Most engine-room fires start when fuel, lubricating or hydraulic oil escapes under pressure and hits a hot surface. SOLAS II-2/4.2.2.5.2 requires every external high-pressure fuel delivery line between the high-pressure fuel pumps and the injectors to be jacketed, with leakage collection and an alarm on a fuel line failure; II-2/4.2.2.5.3 keeps oil fuel lines away from hot surfaces and, as far as practicable, screened or otherwise protected against spray; and II-2/4.2.2.6.1 requires surfaces above 220 °C that could be hit by a fuel system failure to be properly insulated.
Oil fuel pipes from storage, settling and daily service tanks of 500 litres and above situated above the double bottom need a valve on the tank that can be closed from a safe position outside the space (SOLAS II-2/4.2.2.3.4). The same applies to lubricating oil tanks, with the limited exceptions in II-2/4.2.3.2, and the remote control for the emergency generator fuel tank valve must be in a separate location from the controls for tanks in machinery spaces.
Since 1 January 2026, SOLAS II-2/4.2.1.6 (MSC.520(106)) requires a signed and certified declaration from the fuel supplier's representative before bunkering that the oil fuel meets the 60 °C flashpoint rule, stating the test method used; the bunker delivery note must show the flashpoint or a statement that it was measured at or above 70 °C. Purifiers for heated fuel oil are one of the areas a fixed local application fire-fighting system must cover under SOLAS II-2/10.5.6 where that regulation applies.
Engine-room fuel oil fire prevention: what SOLAS requires and what to check
Fire barrier
Main SOLAS basis
Typical defect found
What to check and do
Jacketed high-pressure fuel lines and leak alarm
SOLAS II-2/4.2.2.5.2
Leak collection drain blocked or diverted, float switch seized, alarm bypassed, or a temporary single-wall pipe fitted after maintenance
Keep jackets sealed from pump to injector, keep leak drains open to the collector, test the leak alarm at the maker's and SMS interval, and never run an engine with the alarm bypassed
Hot-surface insulation and spray protection
SOLAS II-2/4.2.2.5.3, II-2/4.2.2.6, II-2/4.2.3 and II-2/4.2.4; guidance in MSC.1/Circ.1321
Exhaust or indicator-cock lagging left off after maintenance, oil-soaked insulation, or spray protection missing on oil pipe joints near hot surfaces
Refit insulation before starting, renew oil-soaked lagging, check for hot spots on rounds, and keep spray protection on fuel, lube and hydraulic joints near hot surfaces
Quick-closing valves, sounding pipes and gauges
SOLAS II-2/4.2.2.3.4, II-2/4.2.2.3.5, II-2/4.2.3.2 and II-2/4.2.2.4
Quick-closing valve wedged or wired open, control air or hydraulic charge low, sounding pipe self-closing device tied open, or a cylindrical gauge glass on an oil fuel tank
Remove any chock or wire at once, check the control charge on rounds, keep sounding devices self-closing, and confirm the emergency generator tank control is at its separate location
Purifiers, remote stops and local application
SOLAS II-2/4.2.5.1, II-2/5.2.2, II-2/10.5.6 and II-2/14; MSC.1/Circ.1432
Oil under floor plates around heaters, remote stop unlabelled or not working, or a local application section valve shut to hide a leaking nozzle
Keep the purifier area clean, test and label remote stops outside the space, and keep local application section valves open and maintained to the fire maintenance plan
1. Jacketed High-Pressure Fuel Lines, Leak Alarms & 220 °C Hot Surfaces
Most serious machinery-space fires do not start in a tank. They start when fuel, lubricating or hydraulic oil escapes from a pressurised joint or a cracked high-pressure pipe and lands on a hot exhaust surface. SOLAS regulation II-2/4.2.2.5.2 requires external high-pressure fuel delivery lines between the high-pressure fuel pumps and the fuel injectors to be protected by a jacketed piping system able to contain fuel from a high-pressure line failure. The jacketed pipe is an outer pipe around the high-pressure pipe, forming a permanent assembly, with a means of collecting leakage and an alarm in case of a fuel line failure.
Treat the leak collector and its alarm sensor as safety equipment in the planned maintenance system. After any injector or fuel pump overhaul, renew the jacket seals as the engine maker's instructions require, make sure the leak drain still runs to the collector rather than an open container, and prove the alarm works before the engine is left running. A blocked drain or a bypassed leak alarm removes the protection the regulation exists to give, and port State inspectors and surveyors look for exactly this kind of defect.
SOLAS II-2/4.2.2.5.3 requires oil fuel lines not to be placed immediately above or near high-temperature units such as boilers, steam pipes, exhaust manifolds and silencers, and, as far as practicable, to be kept away from hot surfaces and ignition sources and screened or otherwise protected against oil spray, with as few joints as possible. Regulation II-2/4.2.2.6.1 requires surfaces above 220 °C that could be hit after a fuel system failure to be properly insulated, and II-2/4.2.2.6.2 requires precautions so that oil escaping under pressure from any pump, filter or heater cannot reach heated surfaces. Regulations II-2/4.2.3 and II-2/4.2.4 apply much of the same discipline to lubricating oil and other flammable oils. IMO MSC.1/Circ.1321 gives guidance on preventing engine-room fires.
Test the main and auxiliary engine high-pressure fuel leak alarms at the interval and by the method in the engine maker's manual and the SMS, and record each test.
After injector, high-pressure pump or fuel rail work, check the jacket seals and confirm the leak drains run to the collector before starting.
On engine-room rounds, look for missing or damaged lagging and hot spots around exhaust manifolds, indicator cocks, turbocharger gas inlets and boiler uptakes.
Renew insulation that has soaked up fuel or lube oil instead of wiping the outside while oil stays trapped underneath.
Check that spray protection is fitted on fuel, lube and hydraulic oil joints, filters and heaters near hot surfaces or machinery air intakes.
If an engine-room fire grows beyond first-aid fire-fighting, the ship has to cut off oil that would otherwise keep flowing from tanks into the space. Under SOLAS II-2/4.2.2.3.4, every oil fuel pipe which, if damaged, would let oil escape from a storage, settling or daily service tank of 500 litres or more situated above the double bottom must have a cock or valve directly on the tank that can be closed from a safe position outside the space concerned. Under II-2/4.2.3.2, the same applies to lubricating oil tanks, except tanks under 500 litres, storage tanks whose valves are closed in normal operation, and cases where an unintended closure of the valve would endanger the safe operation of the main propulsion and essential auxiliary machinery.
Two failures turn quick-closing valves into serious inspection findings. The first is defeating the valve on board: wedges, wire or bolts under a spring-loaded valve after a nuisance trip, or a pneumatic or hydraulic trip reservoir allowed to run down. The second concerns the emergency generator: SOLAS II-2/4.2.2.3.4 requires the remote control for the emergency generator fuel tank valve to be in a separate location from the controls for the other tanks in machinery spaces, so that shutting off fuel during an engine-room fire does not also stop the emergency generator.
Tank gauging and venting complete the picture. SOLAS II-2/4.2.2.3.1 forbids carrying fuel oil, lubricating oil and other flammable oils in forepeak tanks. Under II-2/4.2.2.3.5.1, sounding pipes should not end in machinery spaces; where the Administration accepts that this is impracticable, they may, provided an oil-level gauge is fitted, the pipes end away from ignition hazards or are screened, and each one has a self-closing blanking device with a small-diameter self-closing control cock below it to check that no oil is present before opening. Cylindrical gauge glasses are prohibited (II-2/4.2.2.3.5.2). Under II-2/4.2.2.4, air pipes, overflow pipes and relief valves must discharge where oil or vapour cannot cause a fire or explosion, and never into crew, passenger or machinery spaces; keep any flame screens fitted under the approved arrangement intact.
Walk every fuel oil tank, and every lubricating oil tank the rule covers, of 500 litres or more above the double bottom and confirm nothing blocks the quick-closing valve.
Check the quick-closing valve air receiver or hydraulic accumulator outside the machinery space on rounds as the SMS requires, with clear tank labels and reset instructions.
Operate the quick-closing valves remotely in drills and when surveyors ask, arranging fuel supply to running generators safely beforehand.
Confirm the emergency generator fuel tank control is at its separate location, clearly marked, and not linked to the engine-room shut-off controls.
Test every machinery-space sounding pipe's self-closing device and control cock, and check air and overflow pipe heads and any flame screens on deck.
3. 60 °C Flashpoint, the 2026 Supplier Declaration & Heated Tank Alarms
SOLAS II-2/4.2.1 sets the flashpoint limits for oil fuel. Except where the regulation allows otherwise, no oil fuel with a flashpoint below 60 °C may be used (II-2/4.2.1.1). Emergency generators may use fuel with a flashpoint of not less than 43 °C (II-2/4.2.1.2), and fuel between 43 °C and 60 °C may be permitted under the conditions in II-2/4.2.1.3, for example for emergency fire pump engines and auxiliary machines outside category A machinery spaces. Ships using gas or other low-flashpoint fuels follow the IGF Code. In a periodically unattended machinery space, heated daily service or settling tanks need a high-temperature alarm if the fuel's flashpoint can be exceeded (II-2/4.2.5.2).
Since 1 January 2026, SOLAS II-2/4.2.1.6, added by MSC.520(106), requires ships carrying oil fuel to receive before bunkering a declaration, signed and certified by the oil fuel supplier's representative, that the fuel to be supplied meets the flashpoint requirement of II-2/4.2.1, and stating the test method used to determine the flashpoint. The bunker delivery note must show either the flashpoint or a statement that it has been measured at or above 70 °C. Under II-2/1.2.5 this also applies to ships built before 1 July 2012. On the MARPOL side, MEPC.362(79) added the flashpoint to the bunker delivery note in Annex VI Appendix V, in force since 1 May 2024.
MARPOL Annex VI regulations 14.10 to 14.12 (MEPC.324(75)) also require ships of 400 GT and above to have in-use fuel oil sampling points fitted or designated, normally downstream of the service tank: ships built on or after 1 April 2022 from delivery, older ships by the first IAPP renewal survey on or after 1 April 2023, so that a representative sample can be taken; a low-flashpoint fuel service system needs none. Port State officers use these points while the fuel is hot and under pressure, so keep each point labelled, its valve working and the area clean so a sample can be taken safely.
Before the bunker manifold is opened, obtain and file the supplier representative's signed flashpoint declaration stating the test method (SOLAS II-2/4.2.1.6).
Check that the bunker delivery note shows the flashpoint, or a statement that it was measured at or above 70 °C.
Test high-temperature alarms on heated settling and daily service tanks in periodically unattended machinery spaces, and confirm the set point is as the approved arrangement requires.
During heavy-fuel to distillate changeovers, control fuel heating as the ship's changeover procedure says.
Check the in-use fuel sampling points for labelling, a working valve and a clean, safe place to take the sample.
4. Purifiers, Remote Stops & SOLAS II-2/10.5.6 Local Application Systems
Heated fuel oil purifiers combine hot oil, high-speed bowls, frequent opening for maintenance and pressurised hoses. In a periodically unattended machinery space, SOLAS II-2/4.2.5.1 requires equipment that treats flammable liquids automatically, such as fuel oil purifiers, to have arrangements to prevent overflow spills and, whenever practicable, to be installed in a special space reserved for purifiers and their heaters. Further arrangements (ventilation, doors, drip trays) follow class rules and the approved design. Overhaul bowls, seals and hoses at the purifier maker's intervals with kits suitable for the fuels in use.
SOLAS II-2/5.2.2.3 requires means of stopping forced and induced draught fans, oil fuel transfer pumps, oil fuel unit pumps, lubricating oil service pumps, thermal oil circulating pumps and oil separators (purifiers). Machinery-space power ventilation must be stoppable from two positions, one outside the space (II-2/5.2.2.2), and the controls must be outside the space so a fire there cannot cut them off (II-2/5.2.2.4). Keep each stop labelled with what it serves and be ready to demonstrate it working at surveys and inspections.
SOLAS II-2/10.5.6 applies to passenger ships of 500 GT and above and cargo ships of 2,000 GT and above built on or after 1 July 2002; of ships built earlier, only passenger ships of 2,000 GT and above had to comply, by 1 October 2005 (II-2/1.2.2.4). Machinery spaces of category A above 500 m³ must have, in addition to the main fixed system, an approved fixed water-based or equivalent local application fire-extinguishing system. It protects areas such as the fire hazard portions of internal combustion machinery, boiler fronts, the fire hazard portions of incinerators and purifiers for heated fuel oil, without engine shutdown, evacuation or sealing the space. For ships built before 1 July 2014 the machinery covered is that used for main propulsion and power generation (MSC.338(91)). Periodically unattended spaces need both automatic and manual release; continuously manned spaces need manual release only. Activation must give a visual and distinct audible alarm in the protected space and at continuously manned stations. Maintain the system to the ship's fire maintenance plan under SOLAS II-2/14, using MSC.1/Circ.1432, and never shut a section valve to hide a leaking nozzle.
Keep the purifier area clean and ventilated, heater flanges tight, and drip trays and floor plates free of sludge and oil.
Overhaul purifier bowls, seals and flexible hoses at the maker's intervals and check feed connections for leaks once back at working temperature.
Test the remote stops outside the machinery space for fans, fuel transfer and unit pumps, lube oil service pumps, thermal oil pumps and purifiers, and check each is labelled.
Confirm local application section valves over purifiers, engines and boilers are open, the system is set for automatic release where the space is periodically unattended, and maintenance is logged.
Keep spare jacketed high-pressure fuel pipes, spray protection, quick-closing valve seals and purifier seal kits in the technical stores.
Frequently Asked Questions
Why must the emergency generator fuel quick-closing control be separate from the engine-room controls?
SOLAS II-2/4.2.2.3.4 requires the controls for remote operation of the valve on the emergency generator fuel tank to be in a separate location from the controls for remote operation of the valves on other tanks in machinery spaces. Shutting off fuel to fight an engine-room fire should not also stop the emergency generator and leave the ship without emergency power.
What changed on 1 January 2026 for fuel oil flashpoint documents?
SOLAS II-2/4.2.1.6, added by MSC.520(106), requires the ship to receive before bunkering a declaration, signed and certified by the oil fuel supplier's representative, that the fuel meets the flashpoint requirement of II-2/4.2.1 (normally not less than 60 °C), stating the test method used. The bunker delivery note must show the flashpoint or a statement that it was measured at or above 70 °C.
Which surfaces and pipes need insulation or spray protection under SOLAS II-2/4.2.2?
Surfaces above 220 °C that could be hit after a fuel system failure must be properly insulated (II-2/4.2.2.6.1). External high-pressure fuel lines between the fuel pumps and injectors must be jacketed with leak collection and a failure alarm (II-2/4.2.2.5.2), and oil fuel lines must not be placed immediately above or near high-temperature units and, as far as practicable, must be kept apart from hot surfaces and screened or otherwise protected against spray (II-2/4.2.2.5.3).
When is a fixed local application fire-fighting system needed over fuel oil purifiers?
Under SOLAS II-2/10.5.6, passenger ships of 500 GT and above and cargo ships of 2,000 GT and above built on or after 1 July 2002 (and, of earlier ships, passenger ships of 2,000 GT and above since 1 October 2005) need an approved fixed water-based or equivalent local application system in category A machinery spaces above 500 m³. Purifiers for heated fuel oil are one of the areas it protects, together with boiler fronts, incinerators and the fire hazard portions of internal combustion machinery. Periodically unattended spaces need automatic and manual release.
Try the LNG, Dual-Fuel & Spark-Gas simulator free for 5 minutes, then enrol in the Academy: Self-Paced $395 USD or 6-Week Cohort $995 USD (+ 5% sales tax). Or book a 1-hour consultancy for $350 USD (+ 5% sales tax).
Enquiries welcome at any time. Book our daily 1-hour consultation at 12:00 PM Central Time (CT) ($350 USD + 5% sales tax) or send an enquiry about your vessel, power plant or project.
Have an Academy Access Key? Sign in on this page to send comments or questions straight to our instructors.
/guides/fuel-oil-jacketed-piping-quick-closing-valves-and-purifier-fire-safety-guide/