Marine Fuel Oil Purifier Gravity Disc, Cat-Fines (Al+Si), Water-Seal & In-Use Sampling Troubleshooting Guide

Practical marine fuel oil purifier gravity disc, Al+Si cat-fines removal, water-seal loss, heater stability and MARPOL Reg. 14.10 sampling guide.

← All technical guides · Category: Dual-Fuel & Marine Engines · Updated: · 11 min read

Key Takeaways (TL;DR)

  • A centrifugal disc-stack fuel oil purifier removes free water, rust scale and abrasive catalytic fines (aluminium plus silicon, Al+Si) only when the oil-water interface sits outside the disc stack and inside the outer edge of the top disc. That depends on the right gravity disc for the fuel density at 15 °C (stated on the MARPOL Annex VI Bunker Delivery Note), a steady separating temperature set from the purifier maker's chart, and a low, steady feed rate.
  • ISO 8217:2017 caps Al+Si in the fuel as delivered at 60 mg/kg for the heavier residual grades (RMG and RMK) and lower for the lighter ones (25 mg/kg for RMA 10), and P&I club guidance reports the same 60 mg/kg cap in the 2024 edition. Engine makers generally want far less at the engine inlet, commonly about 15 mg/kg or lower, so the ship's own settling and purification must close the gap. A booster filter that back-flushes more and more often, or rising iron in cylinder scrape-down samples, is an early warning that cat fines or sludge are getting past the purifiers.
  • The main statutory rules around the purifier room are SOLAS II-2/4.2.1 (60 °C minimum flashpoint and, since 1 January 2026, the supplier's flashpoint declaration before bunkering), II-2/4.2.2.6 (hot surfaces above 220 °C), II-2/4.2.5 (purifier overflow protection, a separate purifier space whenever practicable, and heated tank alarms in periodically unattended spaces), II-2/5.2.2 (remote stops), II-2/10.5.6 (local application fire-extinguishing systems where they apply), MARPOL Annex VI regulations 14.8 to 14.13 and 18 (fuel samples, sampling points, BDNs), MARPOL Annex I regulations 12 and 17 (sludge tanks and the Oil Record Book), and IMO Resolution MSC.581(110) for tank entry.

Marine Fuel Oil Purifier, Heater & Backflush Filter Troubleshooting Matrix

Observed Symptom or AlarmAffected SubsystemLikely Mechanical, Thermal or Fuel CauseImmediate Engine-Room Check & Corrective Action
Broken water seal and fuel discharging through the heavy-phase (water) outletGravity-disc purifier bowl and water sealGravity disc bore too large for the actual fuel density, too little sealing water before the feed was opened, fuel overheated, or feed rate surgingShut the feed, check the bowl seal ring and sliding bowl bottom seating, re-check the fuel density at 15 °C on the Bunker Delivery Note against the maker's gravity-disc chart, establish the water seal before opening the feed, and steady the feed temperature
Water-in-oil alarm or free water found when draining the service tankGravity-disc purifier, or gravity-disc-free separator with a water transducerGravity disc bore too small (interface pushed into the disc stack), fouled water transducer, stuck water drain valve, or a tight water-in-fuel emulsionDrain free water from the service tank, check the clean-oil outlet sample, fit the larger disc given by the maker's chart, or clean and test the transducer and drain valve as the maker's manual describes, and reduce the feed rate
Incomplete desludging, or fuel weeping into the sludge outlet after a dischargeSliding bowl bottom and operating-water systemWorn or grooved main seal ring, scale blocking the operating-water passages (hard or untreated operating water), perished seals on the operating slide, or low operating-water pressureCheck operating-water pressure, strainer and water quality against the maker's specification, clean the operating-water nozzles under the bowl, renew the main seal ring and slide seals, and confirm the bowl closes cleanly after each discharge
High vibration, or slow run-up and low motor currentBowl assembly, disc-stack compression and friction driveUneven sludge cake left after a failed discharge, bowl parts not assembled to their balance marks, too little disc-stack compression, worn spindle bearing springs, or slipping friction padsShut the feed and let the separator run down from a safe position without forcing the brake outside the maker's instructions, then open the bowl, clean out the sludge, restore disc-stack compression as the manual describes, and check the spindle bearings
Hunting purifier inlet temperature and unsteady clean-oil back-pressureSteam or electric pre-heater and its control loopWaterlogged steam trap on the heater drain, sticking temperature control valve, fouled heater surfaces, or a starved feed pump suction strainerProve the steam traps and condensate return, clean suction strainers, service or tune the temperature controller as the maker's manual describes, and confirm the separating temperature matches the fuel viscosity on the maker's chart
Automatic backflush filter in the booster module flushing more and more oftenPressurised fuel supply module after the service tankSludge from mixing incompatible bunkers in settling or service tanks, purifier feed rate too high, dirty disc stack, or dirty oil returned to the service systemDo not run on the manual bypass strainer alone, run both purifiers at a lower feed rate, clean the disc stacks, have the fuel tested for stability and Al+Si, and check the backflush filter elements for damage

1. Gravity Disc Selection, the Oil-Water Interface & Water-Transducer Separators

A disc-stack purifier separates water droplets and dense solids from heated fuel by spinning a thin layer of oil between conical discs at high speed. Stokes' law explains what helps: the separation speed of a particle rises with the density difference between particle and oil, with the square of the particle diameter and with the centrifugal force, and falls as the oil viscosity rises. Time spent inside the disc stack also matters. So if the bowl runs slow (slipping drive, wrong supply frequency) or the feed rate is pushed towards the pump's maximum, the smallest water droplets and cat-fine particles are carried out with the clean oil.

In a conventional gravity-disc purifier, the balance between the lighter oil column and the heavier water column sets where the oil-water interface sits. The normal start sequence is: bowl up to full speed, bowl closed, sealing water admitted to form the water seal, and only then the fuel feed opened. If the feed opens before the seal forms, untreated fuel goes straight out through the water outlet.

The gravity disc (regulating ring) is chosen so that the interface sits outside the disc stack but inside the outer edge of the top disc. A disc whose bore is too large for the fuel, or a sudden rise in feed temperature, moves the interface outward until the water seal breaks and fuel is lost to the sludge tank. A disc whose bore is too small, or cold and thick fuel, moves the interface inward into the disc stack, which cuts the separating area and lets water through with the clean oil. Choose the disc from the maker's chart or calculation tool, using the density at 15 °C from the Bunker Delivery Note (MARPOL Annex VI Appendix V requires density testing to ISO 3675 or ISO 12185), the planned separating temperature and the actual feed rate. Viscosity is not a required BDN entry, so take it from the supplier's documents or the laboratory report.

Gravity-disc-free separators avoid changing discs for each bunker. They run as a clarifier with the water outlet closed. Separated water and solids build up at the bowl wall until water reaches the disc stack and starts to leave with the clean oil, where a water transducer in the clean-oil outlet detects it. The control system then either drains the water through a drain valve or starts a sludge discharge. Sludge films and emulsified water can coat the transducer, so clean and check it, and the clean-oil back-pressure setting, at the intervals in the maker's manual.

  • Check the density at 15 °C on the MARPOL Annex VI Bunker Delivery Note, and the viscosity on the supplier's documents or laboratory report, before transferring a new bunker to the settling tank.
  • On conventional purifiers, confirm the fitted gravity disc against the maker's chart for the actual density, separating temperature and feed rate.
  • Confirm full bowl speed and a settled motor current, and establish the water seal before opening the feed after every start.
  • On gravity-disc-free separators, clean and test the water transducer, water drain valve and back-pressure setting at the interval in the maker's manual.

2. Catalytic Fines (Al+Si) Removal, Low Feed Rates & Settling Tank Discipline

Catalytic fines (cat fines) are hard particles of refinery catalyst, made mainly of aluminium and silicon, that end up in residual blend components. They are measured as Al+Si in mg/kg. Gard reports particle sizes of about 1 to 75 micrometres. Because they are so hard, they embed in and scratch the moving surfaces of fuel pumps, injectors, piston rings and cylinder liners, causing fast abrasive wear and scuffing.

Keep two limits apart: the limit on fuel as delivered and the level that is safe at the engine. ISO 8217:2017 (Table 2) sets the maximum Al+Si for delivered residual fuel at 60 mg/kg for RMG and RMK grades, 50 mg/kg for RME 180, 40 mg/kg for RMB 30 and RMD 80, and 25 mg/kg for RMA 10, and Gard reports that the 60 mg/kg limit for viscous grades is kept in ISO 8217:2024. Engine makers generally recommend much less at the engine inlet, commonly about 15 mg/kg or lower; follow your own engine maker's figure. The difference has to be removed on board by settling and purification. P&I guidance also advises sending the bunker sample for laboratory testing and waiting for the result before burning the new fuel whenever the fuel on board allows it.

Cat-fine removal starts in the tanks. Load new bunkers into empty tanks where possible rather than on top of a different fuel, and test compatibility first if mixing cannot be avoided, because unstable mixtures drop sludge that fouls purifier discs and filters. Keep settling tank temperature steady so that water and heavier particles can settle, and stay within the flashpoint limits in the maker's manual and the Safety Management System. Drain water and sediment from settling and service tanks regularly (Gard advises at least twice a day), because rough weather can stir up old sediment that is rich in cat fines.

Inside the purifier, the smallest particles are the hardest to catch, because their settling speed falls with the square of their diameter. So run the purifiers continuously at a feed rate close to the engines' actual consumption (P&I guidance suggests capacity of about daily consumption plus 10%) rather than one unit at high flow switching on and off with tank level. P&I guidance advises considering both purifiers, especially when the laboratory reports high Al+Si: in parallel at a low feed rate each or in series, as the maker's instructions and the installed piping allow. In the booster module, log how often the automatic backflush filter flushes and its differential pressure every watch. If flushing increases after a tank change, take samples before and after the purifiers for laboratory Al+Si and sediment comparison, and check cylinder scrape-down samples for signs of abrasive wear.

  • Keep new residual or VLSFO bunkers segregated until the laboratory ISO 8217 report confirms Al+Si, sediment, water and flashpoint, whenever the fuel on board allows.
  • When Al+Si is high, use both purifiers (in parallel at a low feed rate, or in series where the plant allows) with a steady feed temperature, and meet the engine maker's inlet figure.
  • Drain water and sediment from settling and service tanks regularly, as the Safety Management System requires.
  • Record backflush filter flushing counts and differential pressure each watch, investigate any increase, and never run on the manual bypass strainer alone.

3. Bowl Desludging, Operating Water & Vibration Checks

Self-cleaning purifiers discharge sludge without stopping, using a sliding bowl bottom worked by water pressure. During separation, closing water under the sliding bottom holds it up against the main seal ring. When a discharge is due (by timer or, on transducer machines, by the control system), the feed is stopped, displacement water may be added so that less oil is lost, and opening water lets the sliding bottom drop for a moment. Sludge and cat fines are thrown out through the ports at the bowl wall, and closing water then re-seals the bowl.

This only works with clean operating water and clear passages. Hard or untreated water leaves scale under the hot bowl and can block the operating-water passages or stick the operating slide. A blocked closing-water supply, a perished slide seal or a grooved main seal ring stops the bowl closing tightly after a discharge, so fuel and water weep into the sludge outlet and fill the sludge tank quickly. A blocked opening-water strainer or low opening-water pressure gives a partial discharge and leaves uneven sludge in the bowl.

Uneven sludge or an assembly error shows up as vibration during run-up or just after a discharge. Never stand next to a purifier that is vibrating badly. Shut the feed, isolate the power and let it run down from a safe position, using the brake only as the maker's manual allows. At bowl overhauls, clean the discs with the cleaning agent and tools the maker approves (not steel scrapers), restore disc-stack compression as the manual describes, assemble the bowl parts to their balance marks, and check the spindle bearings, springs and oil bath.

A slipping friction drive (oil or water on the pads) gives slow acceleration and a low bowl speed, which reduces cat-fine removal without any alarm. Before starting any purifier, check that the sludge outlet line and any sludge transfer arrangement are clear and the sludge tank vent is open. A blocked sludge outlet can push hot vapour and sludge past the bowl seals into the drive housing and contaminate the gear oil.

  • Check operating-water pressure and water quality against the maker's specification to prevent scale under the sliding bowl bottom.
  • Watch the motor current during scheduled discharges to confirm the bowl opens and re-seals cleanly without weeping afterwards.
  • At overhauls, assemble bowl parts to their balance marks and restore disc-stack compression as the maker's manual describes.
  • Check the drive housing oil sight glass each watch for milky oil or metal particles, and keep sludge outlets and tank vents clear.

4. Pre-Heater Stability, Flashpoint Rules, SOLAS II-2/10.5.6 Local Application Systems & Remote Stops

Good separation needs a steady oil viscosity at the bowl, not one universal temperature. For high-viscosity residual fuel, purifier makers' charts commonly call for about 98 °C (P&I guidance quotes the same figure), kept below the boiling point of the sealing water. Lower-viscosity VLSFO, ULSFO and distillates need lower temperatures from the maker's chart. Small swings in heater outlet temperature, from a waterlogged steam trap, an oversized steam valve, a fouled electric heater or a badly tuned controller, change both viscosity and density at once, which leads to repeated water-seal losses and lets cat fines through.

SOLAS II-2/4.2.1.1 says no oil fuel with a flashpoint below 60 °C may be used, with limited exceptions: not less than 43 °C in emergency generators (4.2.1.2), conditional use of 43 to 60 °C fuel, for example for emergency fire pump engines and auxiliaries outside category A machinery spaces (4.2.1.3), and other cases the regulation sets out. Since 1 January 2026, SOLAS II-2/4.2.1.6 (added by IMO Resolution MSC.520(106), and applied to ships built before 1 July 2012 by II-2/1.2.5) requires the ship to receive, before bunkering, a declaration signed and certified by the supplier's representative that the fuel meets 4.2.1, with the flashpoint test method used. The Bunker Delivery Note must show either the flashpoint or a statement that it was measured at or above 70 °C (MARPOL Annex VI Appendix V as amended by MEPC.362(79), in force 1 May 2024, with ISO 2719 given as the test method). In periodically unattended machinery spaces, heated service or settling tanks need a high-temperature alarm if the fuel's flashpoint can be exceeded (II-2/4.2.5.2).

SOLAS II-2/4.2.5.1 applies to periodically unattended machinery spaces: equipment that treats flammable liquids automatically, such as fuel oil purifiers, must have arrangements to prevent overflow spills and, whenever practicable, be installed in a special space reserved for purifiers and their heaters. Oil fuel lines must be kept away from hot surfaces and, as far as practicable, screened or otherwise protected against spray or leaks onto ignition sources (II-2/4.2.2.5.3). Surfaces above 220 °C that could be hit by fuel from a system failure must be properly insulated (II-2/4.2.2.6.1), and precautions are needed so that oil escaping under pressure from a pump, filter or heater cannot reach heated surfaces (II-2/4.2.2.6.2). Means must be provided to stop machinery space ventilating fans (II-2/5.2.2.2) and forced and induced draught fans, oil fuel transfer pumps, oil fuel unit pumps, lubricating oil service pumps, thermal oil circulating pumps and oil separators (purifiers) (II-2/5.2.2.3). These controls, and the remote closing of tank valves under II-2/4.2.2.3.4 (storage, settling or daily service tanks of 500 litres and above situated above the double bottom), must be outside the space concerned (II-2/5.2.2.4).

SOLAS II-2/10.5.6 applies to passenger ships of 500 GT and above and cargo ships of 2,000 GT and above with category A machinery spaces above 500 m³. It applies to ships built on or after 1 July 2002, and earlier passenger ships of 2,000 GT and above had to comply by 1 October 2005 (II-2/1.2.2.4). These spaces need an approved fixed water-based or equivalent local application fire-extinguishing system that protects, among other areas, purifiers for heated fuel oil, without the need to stop engines, evacuate people or seal the space. In periodically unattended spaces the system must have both automatic and manual release, and activation must give a visual and distinct audible alarm in the protected space and at continuously manned stations. Maintain it under SOLAS II-2/14, using MSC.1/Circ.1432 as the basis for inspection and testing, keep its valves in the positions the approved arrangement requires so it stays ready on automatic, and keep the bilge under the purifiers free of oil.

  • Check the supplier's pre-bunkering flashpoint declaration (SOLAS II-2/4.2.1.6) and the BDN flashpoint entry, and test the high-temperature alarms on heated settling and service tanks.
  • Check heater steam traps, control valves and insulation, and set the separating temperature from the fuel viscosity and the maker's chart.
  • Inspect flexible hoses, spray screening, drip trays, bilge alarms and the insulation on any surface above 220 °C that fuel could reach (SOLAS II-2/4.2.2.6).
  • Test the remote stops outside the space for purifiers, fuel pumps and ventilation fans (SOLAS II-2/5.2.2), and confirm the SOLAS II-2/10.5.6 local application system over the purifiers is set for automatic operation where required.

5. MARPOL Reg. 14.10 Sampling Points, ORB Code C Sludge Records & MSC.581(110) Tank Entry

MARPOL Annex VI regulation 14.10 (added by IMO Resolution MEPC.324(75)) requires every ship subject to regulations 5 and 6 of the Annex (the ships that need IAPP surveys and certification) to have sampling point(s) fitted or designated for taking representative samples of the fuel oil in use, taking into account IMO guidelines (MEPC.1/Circ.864/Rev.1). Ships built before 1 April 2022 had to comply by their first IAPP renewal survey on or after 1 April 2023 (14.11). Regulation 14.12 exempts the fuel oil service system for a low-flashpoint fuel, and since 1 August 2025 (as amended by MEPC.385(81)) also one used for a gas fuel. Regulations 14.8 and 14.9 cover how in-use and onboard samples are analysed and sealed (onboard sampling guidelines: MEPC.1/Circ.889). Under MEPC.1/Circ.864/Rev.1, a sampling point should be easy and safe to reach, downstream of the service tank in use, clearly marked, shielded from heated surfaces and electrical equipment, and drained to a safe place.

MARPOL Annex VI regulation 18.6 requires the Bunker Delivery Note to be kept on board, readily available for inspection, for three years after delivery. Under regulation 18.8.1, the MARPOL delivered sample is sealed and signed and kept under the ship's control until the fuel is substantially consumed, and in any case for at least 12 months from delivery. IMO guidelines MEPC.182(59) say it should be drawn continuously at the receiving ship's inlet bunker manifold throughout the delivery, and should be not less than 400 ml. Under MARPOL Annex VI Appendix VI (as revised by MEPC.324(75)), a delivered sample meets the requirement only if the laboratory result is not above the limit itself (0.50% or 0.10% m/m), while in-use and onboard samples analysed under regulation 14.8 are allowed the 0.59R test margin (up to 0.53% and 0.11% m/m).

Sludge from purifier discharges and tank drains falls under MARPOL Annex I regulation 12: every ship of 400 GT and above needs sludge tank(s) of adequate capacity, with a designated disposal pump, no discharge connections to the bilge system, bilge holding tanks, tank top or oily water separators (apart from permitted drains), and no direct connection overboard other than the standard discharge connection of regulation 13. Regulation 17 requires an Oil Record Book Part I on oil tankers of 150 GT and above and other ships of 400 GT and above, kept for three years after the last entry (an electronic record book may be used where the Administration has approved it, with MEPC.312(74) as the guidelines). Under Code C, sludge tank quantities (C 11.1 to 11.3) are recorded weekly, manual collections go under C 11.4, and disposals under C 12.1 (reception facility), C 12.2 (another tank), C 12.3 (incinerated) or C 12.4 (other method). The sludge tanks named should match section 3 of the IOPP Certificate Supplement. Under IMO Resolution A.1206(34), port State control officers may weigh the quantity of oil residues generated against sludge and bilge tank capacity and inspect the Oil Record Book, and its Appendix 2 lists among deficiencies that may warrant detention insufficient remaining sludge tank capacity for the intended voyage, no Oil Record Book available, an unauthorised discharge bypass, and oil residue accumulated in machinery spaces. Under ISM Code 10.3, the Company should identify equipment and technical systems whose sudden failure may result in hazardous situations, and its SMS should include regular testing of standby arrangements.

When crew open a settling tank, service tank, overflow tank or sludge tank for cleaning or heating-coil repair, follow IMO Resolution MSC.581(110) (adopted 27 June 2025), the revised enclosed space entry recommendations that supersede A.1050(27) (the MSC invited the IMO Assembly to revoke it). SOLAS XI-1/7 requires a portable atmosphere testing instrument able to measure oxygen, flammable gases or vapours, hydrogen sulphide and carbon monoxide, with means to calibrate it, and SOLAS III/19.3.3 requires crew with entry or rescue duties to take part in an enclosed space entry and rescue drill at least every two months. Isolate and blank the steam coils and fuel or sludge lines, let the tank cool, and ventilate it thoroughly. MSC.581(110) advises stopping ventilation for about 10 minutes before the pre-entry tests, testing at several levels, and getting steady readings of 20.9% oxygen, CO2 below 0.5%, below 1% of the lower flammable limit where flammable vapour is possible, and toxic gases below 50% of their occupational exposure limit. Ventilation then continues during entry: its example permit becomes invalid if ventilation stops. The permit's validity should be set by the risk assessment and never be longer than eight hours, and it is void if people leave the space unattended. For shipowners, technical superintendents and Chief Engineers reviewing purifier cat-fine performance or PSC readiness, Marvel Solutionz offers remote engineering support at $350 USD for a 1-hour consultancy (+ 5% sales tax), plus the LNG, Dual-Fuel (DF) & Spark-Gas (SG) Academy at $395 USD self-paced (+ 5% sales tax) and Corporate Team Training for up to 10 engineers at $3,500 USD (+ 5% sales tax).

  • Inspect the MARPOL Annex VI Reg. 14.10 in-use sampling points: clearly marked, safe to reach, shielded from hot surfaces and electrical equipment, and drained to a safe place.
  • Check that BDNs are kept for three years (Reg. 18.6) and that sealed MARPOL delivered samples are kept until the fuel is substantially consumed and for at least 12 months (Reg. 18.8.1).
  • Reconcile weekly sludge tank quantities (C 11.1 to 11.3) and disposals (C 12.1 to 12.4) in Oil Record Book Part I against the tanks in the IOPP Supplement.
  • Before entering any fuel or sludge tank: isolate steam and piping, test the atmosphere at several levels with a calibrated SOLAS XI-1/7 instrument (20.9% O2, < 0.5% CO2, < 1% LFL, < 50% OEL), and issue a permit of no more than eight hours under MSC.581(110).

Frequently Asked Questions

How do engineers select the right gravity disc and prevent water-seal loss on a fuel oil purifier?

Choose the gravity disc (regulating ring) from the purifier maker's chart or calculation tool, using the density at 15 °C on the MARPOL Annex VI Bunker Delivery Note, the separating temperature and the feed rate. Bring the bowl to full speed, close it and admit sealing water to form the seal before opening the feed. A bore that is too large pushes the interface outward and breaks the water seal; a bore that is too small pushes it into the disc stack and lets water through with the clean oil.

Why can fuel within the ISO 8217 cat-fines limit still damage an engine?

ISO 8217:2017 allows up to 60 mg/kg of aluminium plus silicon in delivered RMG and RMK residual fuel (less for lighter grades, for example 25 mg/kg for RMA 10), but engine makers generally recommend far less at the engine inlet, commonly about 15 mg/kg or lower. The ship has to remove the difference. Keep incompatible bunkers apart, keep settling and heater temperatures steady within maker and SMS limits, drain settling and service tanks regularly, and when Al+Si is high use both purifiers at a low feed rate (in parallel, or in series where the plant allows) rather than one unit at high flow.

Should every fuel oil purifier run at 98 °C?

No. About 98 °C is the figure purifier makers' charts commonly give for high-viscosity residual fuel, kept below the boiling point of the sealing water. Lower-viscosity VLSFO, ULSFO and distillates need lower temperatures from the maker's chart. Heated settling and service tanks must also stay within flashpoint limits: SOLAS II-2/4.2.1.1 sets a 60 °C minimum flashpoint for oil fuel, and II-2/4.2.5.2 requires a high-temperature alarm on heated tanks in periodically unattended machinery spaces if the flashpoint can be exceeded.

What makes an automatic backflush fuel filter in the booster module flush continuously?

Frequent flushing means more solids or unstable sludge are leaving the service tank. Common causes are incompatible bunkers mixed in settling or service tanks, a purifier feed rate that is too high or a heater temperature that hunts, a broken water seal or dirty disc stack, or dirty oil returned to the service system. Run the purifiers at a lower feed rate, clean the filter elements as the filter maker's manual describes, and never run on the manual bypass strainer alone.

When did MARPOL Annex VI in-use fuel oil sampling points become mandatory?

Regulation 14.10 (added by IMO Resolution MEPC.324(75)) requires every ship subject to regulations 5 and 6 of Annex VI to have in-use sampling point(s) fitted or designated, taking into account MEPC.1/Circ.864/Rev.1. Ships built before 1 April 2022 had to comply by the first IAPP renewal survey on or after 1 April 2023 (Reg. 14.11). Reg. 14.12 exempts the fuel oil service system for a low-flashpoint fuel, and since 1 August 2025 (as amended by MEPC.385(81)) also one used for a gas fuel.

What fire-safety and tank-entry rules apply to fuel oil purifier rooms and sludge tanks?

In periodically unattended machinery spaces, SOLAS II-2/4.2.5.1 requires automatic purifiers to have overflow protection and, whenever practicable, a special purifier space. Purifiers and fuel pumps must have stops outside the space (II-2/5.2.2.3 and 5.2.2.4), surfaces above 220 °C that fuel could reach must be properly insulated (II-2/4.2.2.6.1), and where SOLAS II-2/10.5.6 applies (passenger ships of 500 GT and above and cargo ships of 2,000 GT and above built on or after 1 July 2002 with category A machinery spaces above 500 m³, plus earlier passenger ships of 2,000 GT and above from 1 October 2005), a fixed water-based or equivalent local application system protects purifiers for heated fuel oil. Fuel or sludge tank entry should follow IMO Resolution MSC.581(110): 20.9% oxygen, CO2 below 0.5%, below 1% LFL and below 50% OEL, with a permit of no more than eight hours that is void if the space is left unattended.

Regulatory & Technical Sources

Train with Marvel Solutionz or get expert help

Try the LNG, Dual-Fuel & Spark-Gas simulator free for 5 minutes, then enrol in the Academy: Self-Paced $395 USD or 6-Week Cohort $995 USD (+ 5% sales tax). Or book a 1-hour consultancy for $350 USD (+ 5% sales tax).