Where an EDG is fitted, SOLAS II-1/42 (passenger ships) normally mandates 36-hour supply, 45-second automatic full-load start, and a 30-minute transitional battery. SOLAS II-1/43 (cargo ships) normally mandates 18-hour supply (3 hours at muster and embarkation stations) plus either 45-second auto-start or a 30-minute transitional battery.
SOLAS II-1/44 mandates cold starting at 0 °C (or Administration-acceptable heating) and at least three consecutive starts on auto-start sets. Hulls built from 1 October 1994 onwards must guard stored energy from critical depletion (unless a second independent starter exists) plus a second source for three further starts inside 30 minutes unless proven manual starting applies.
In the IACS 2025 emergency power CIC (36,723 ships inspected, 853 vessels logging 995 recorded failure/malfunction deficiencies), quick-closing valves (21.51%), control circuits (16.08%), starting setups (13.67%), wrong selector switches (12.06%), and ACBs (11.66%) ranked highest.
IACS concluded that missing SMS controlled blackout procedures conflict with SOLAS II-1/42.7 and 43.7, while simulated RTS or sequence tests skip real blackout circuit paths and create false readiness. Prepare for A.1207(34) surveys and A.1206(34) PSC checks with documented controlled blackout routines.
SOLAS Chapter II-1 (Regs. 42, 43, 44, 29.14) and Chapter II-2 (Reg. 4.2) Emergency Power Baselines
Statutory Parameter
Passenger Ships (SOLAS II-1/42)
Cargo Ships (SOLAS II-1/43)
Starting, Fire & Steering Cross-Rules
Core endurance & embarkation lighting
36 h across emergency lighting, muster and embarkation stations, navigation lights, radio, alarms, and pumps (42.2.1 to 42.2.4). Short-voyage floor 12 h with Administration approval (42.2.7).
18 h across emergency lighting, navigation lights, radio, alarms, and EDG-fed fire pump (43.2.2 to 43.2.5), plus 3 h at muster and embarkation stations and over the sides (43.2.1). Short-voyage floor 12 h for 18 h items (43.2.6.2).
Tankers built from 1 July 2002 onwards require 18 h emergency lighting in cargo pump-rooms (43.2.2.7 via MSC.99(73)). Passenger power-operated watertight doors and lift recovery need 30 min (42.2.6).
45 s automatic start & 30 min transitional source
EDG ships: mandatory 45 s auto-start at full rated load (42.3.1.2) PLUS mandatory 30 min transitional battery within +/-12% voltage (42.3.1.3 & 42.4). Battery-only option under 42.3.2.
EDG ships: either 45 s auto-start taking required load without a transitional battery, OR a 30 min transitional battery (+/-12% voltage) without mandatory auto-start (43.3.1.2, 43.3.1.3 & 43.4). Battery option under 43.3.2.
Steering backup (II-1/29.14, required rudder stock over 230 mm at tiller, excl. ice): auto within 45 s for at least 30 min continuous (10,000 GT and upwards) or 10 min (other covered ships), from emergency power or dedicated local supply.
Location, inclination & collision bulkhead
Above uppermost continuous deck, reachable readily from open deck, never ahead of collision bulkhead (42.1.2). Full rated power upright, up to 22.5° list and 10° trim, or combined (42.6).
Above uppermost continuous deck, reachable readily from open deck, aft of collision bulkhead unless Administration permits otherwise in exceptional circumstances (43.1.2). Full output up to 22.5° list and 10° trim (43.6).
ESB close as practicable to emergency power source, inside EDG space unless impaired (42.5.1 to .2 / 43.5.1 to .2). Keep Reg. 42 or 43 batteries outside ESB space with discharge indicator on MSB or inside MCR (42.5.3 / 43.5.3).
Starting energy & 0 °C cold-start capability
Governed by SOLAS II-1/44 and MSC.27(61) (42.3.3 disapplies older depletion text for hulls built from 1 Oct 1994 onwards).
Governed by SOLAS II-1/44 and MSC.27(61) (43.3.3 disapplies older depletion text for hulls built from 1 Oct 1994 onwards).
Ready 0 °C cold start or Administration-acceptable heating (44.1). Auto-start sets: at least 3 consecutive starts (critical-depletion protection from 1 Oct 1994 unless a 2nd independent starter exists) plus 2nd source for 3 more inside 30 min unless manual start proven effective (44.2 & 44.2.1). Starting, charging, and storage gear dedicated inside EDG room (44.3.3).
Fuel flashpoint & quick-closing shut-off valve
Independent supply of fuel with closed-cup flashpoint at least 43 °C (42.3.1.1 & II-2/4.2.1.2), vs 60 °C baseline (II-2/4.2.1.1).
Independent supply of fuel with closed-cup flashpoint at least 43 °C (43.3.1.1 & II-2/4.2.1.2), vs 60 °C baseline (II-2/4.2.1.1).
Daily service, settling, or storage fuel tanks of 500 l capacity or greater located above double-bottom tankage need tank-mounted valves on pipes whose damage could release oil, closed safely outside the compartment, with EDG controls in a separate location from machinery-space tank controls (II-2/4.2.2.3.4).
Dead-ship recovery & periodic full-system test
Hulls built from 1 July 1998 onwards needing electricity to restore propulsion must recover inside 30 min (42.3.4). Complete emergency setup needs periodic testing (42.7).
Hulls built from 1 July 1998 onwards needing electricity to restore propulsion must recover inside 30 min (43.3.4). Complete emergency setup needs periodic testing (43.7).
IMO Unified Interpretations (MSC.1/Circ.1572/Rev.2 Secs. 4.1 & 7, consolidating MSC.1/Circ.1464/Rev.1) state that EDG stored starting energy is not to be used directly for starting propulsion, main power, or essential auxiliaries, clock steamships to first boiler light-off, and list nine port-use safeguards.
1. SOLAS II-1/42 and 43 Architecture: Endurance, 45-Second Start and Transitional Power
An emergency diesel generator (EDG) holds emergency lighting, radios, fire protection, and vital controls alive when main electrical generation fails. Under SOLAS Chapter II-1, passenger ships follow Regulation 42 while cargo ships follow Regulation 43.
Engineers can blur those two rules during preparation, yet three structural splits shape survey scope. First, paragraphs 42.1.2 and 43.1.2 place the emergency source, any transforming gear, the transitional source, and both the emergency and emergency lighting switchboards above the uppermost continuous deck, reachable readily from open-deck spaces.
Neither ship type may place those spaces ahead of the collision bulkhead, except that paragraph 43.1.2 permits cargo-ship waivers in exceptional circumstances. Paragraphs 42.1.3 and 43.1.3 require arrangements satisfactory to the Administration so fire or casualty in main power, switchboard, or Category A spaces will not disrupt emergency supply, control, or distribution, avoiding contiguous boundaries as far as practicable.
Second, statutory endurance differs sharply. Passenger ships under paragraphs 42.2.1 to 42.2.4 normally require 36 hours across emergency lighting, muster and embarkation stations, navigation lights, internal alarms, fire detection, fire-door release circuits, and designated emergency pumps (including any sprinkler pump). GMDSS radio feeds apply to ships built from 1 February 1995 onwards.
Cargo ships under paragraphs 43.2.2 to 43.2.5 normally require 18 hours for emergency lighting, navigation lights, GMDSS radio (from 1 February 1995), alarms, fire detection, and an EDG-fed fire pump. Paragraphs 42.2.3 and 43.2.4 exclude loads carrying an independent 36-hour or 18-hour emergency battery. Cargo muster, embarkation, and over-side lighting requires 3 hours (43.2.1), while tankers built from 1 July 2002 onwards require 18-hour cargo pump-room emergency lighting (43.2.2.7 via MSC.99(73)).
Where satisfied that an adequate safety standard is attained on regular short voyages, an Administration may accept a shorter endurance period not under 12 hours under paragraphs 42.2.7 and 43.2.6.2 (leaving 43.2.1 intact). Passenger ships also cover 30 minutes for power-operated watertight doors with indicators and warnings (42.2.6.1) and lift-car recovery to deck level, which may run sequentially (42.2.6.2).
Third, although paragraphs 42.3.2 and 43.3.2 allow an accumulator battery as the emergency source, EDG-equipped passenger and cargo ships pair automatic starting and transitional batteries differently. EDG-equipped passenger ships need both automatic starting at full rated load inside 45 seconds (42.3.1.2) and a 30-minute transitional battery holding voltage within 12% of nominal without recharge (42.3.1.3 and 42.4).
EDG-equipped cargo ships follow an either-or rule. Paragraph 43.3.1.2 mandates automatic starting unless a transitional battery exists, while paragraph 43.3.1.3 mandates that 30-minute battery unless an auto-start EDG takes required loads inside 45 seconds. Neither Regulation 42.4 nor 43.4 places shipborne navigational equipment (42.2.3.2 or 43.2.4.2) in the mandatory minimum transitional-battery list.
Switchboard layout aligns across paragraphs 42.5 and 43.5. The emergency switchboard sits close as practicable to the emergency power source (42.5.1 / 43.5.1), and inside the EDG space unless operation would be impaired (42.5.2 / 43.5.2). Paragraphs 42.5.3 and 43.5.3 keep Regulation 42 or 43 batteries outside the switchboard room and require a discharge indicator either on the main switchboard or inside the machinery control room.
Under paragraphs 42.5.4 and 43.5.4, the interconnector feeder carries overload and short-circuit protection at the main switchboard and opens at the emergency switchboard when main supply fails. Paragraphs 42.5.5 and 43.5.5 shed non-emergency circuits automatically where necessary to keep emergency circuits powered. Paragraphs 42.6 and 43.6 mandate full rated output upright, up to 22.5° list, 10° trim, or combined.
Two linked SOLAS machinery rules also tie into emergency power. Where required rudder stock at the tiller exceeds 230 mm (excluding ice strengthening), SOLAS II-1/29.14 mandates an automatic 45-second alternative steering supply from the ship's emergency electrical power source or a dedicated steering-compartment source. That supply must deliver at least 30 minutes continuous service on vessels of 10,000 GT and upwards, or 10 minutes on smaller covered ships.
For hulls built from 1 July 1998 onwards needing electrical power to restore propulsion from dead ship, paragraphs 42.3.4 and 43.3.4 require capacity, with other machinery as appropriate, inside 30 minutes after blackout. IMO Unified Interpretation MSC.1/Circ.1572/Rev.2 (consolidating MSC.1/Circ.1464/Rev.1) Section 4.1 (interpreting II-1/26.4) allows an EDG complying with Regulation 44, IACS SC185 and IACS SC124 to be used to restore the main plant, provided the power supplies needed for engine operation are protected to a similar level as the starting arrangements. Section 7 states that EDG stored starting energy is not to be used directly for starting propulsion, main power, or other essential auxiliaries, clocks steamships to first boiler light-off, and lists nine port-use safeguards.
Confirm the statutory baseline on the one-line diagram: EDG passenger (II-1/42: 36 h, 45 s, 30 min battery), EDG cargo (II-1/43: 18 h, 3 h embarkation, 45 s or battery), or battery-only source (42.3.2 / 43.3.2).
Verify Regulation 42 or 43 emergency and transitional accumulator batteries sit outside the emergency switchboard room, and test their discharge indicator either on the main switchboard or inside the machinery control room (II-1/42.5.3 or 43.5.3).
Confirm the interconnector feeder carries overload and short-circuit protection at the main switchboard, opens at the emergency switchboard on main-power failure, and sheds non-emergency circuits where necessary (II-1/42.5.4 to .5 or 43.5.4 to .5).
Check whether the vessel relies on emergency power for SOLAS II-1/29.14 steering backup (at least 30 min or 10 min continuous) and dead-ship recovery inside 30 minutes on hulls built from 1 July 1998 onwards (II-1/42.3.4 or 43.3.4).
An automatic transfer relay cannot save a dead ship if the emergency prime mover refuses to crank. SOLAS Chapter II-1 Regulation 44 governs cold-weather readiness, stored-energy capacity, recharge feeds, and space dedication for emergency generating sets.
Paragraph 44.1 requires emergency generating sets to start readily in cold condition at 0 °C. If that is impracticable, or if lower ambient temperatures are likely, heating arrangements acceptable to the Administration must be maintained for ready starting (such as jacket water or space heaters in shipboard practice).
Under paragraph 44.2, automatically started EDGs need Administration-approved starting gear holding energy for at least three consecutive starts. For ships built from 1 October 1994 onwards, IMO Resolution MSC.27(61) inserted paragraph 44.2.1 and disapplied the earlier complete-depletion sentence in paragraphs 42.3.1.2 and 43.3.1.2 via paragraphs 42.3.3 and 43.3.3.
On hulls built from 1 October 1994 onwards, paragraph 44.2.1 replaces the second sentence of paragraph 44.2. Primary stored energy must be protected against critical depletion from automatic starting unless a second independent starting means is fitted. A second energy source must also deliver three further starts inside 30 minutes unless proven manual starting applies.
SOLAS II-1/44 prescribes no fixed voltage or starter brand. Subject to class and maker approval, installations may combine electric battery starting with a second battery bank, a hydraulic starter, or a dedicated air bottle. Where SOLAS does not require auto-starting, paragraph 44.4.1 permits proven manual cranking, inertia starters, hand-charged hydraulic accumulators, or powder cartridges. Where manual starting is impracticable, paragraph 44.4.2 mandates paragraphs 44.2 and 44.3 compliance with manual initiation.
Paragraph 44.3 requires stored starting energy to stay maintained at all times. Electric and hydraulic starters recharge from the emergency switchboard (44.3.1). Compressed-air starting recharges via main or auxiliary air bottles through a check valve, or via an emergency air compressor powered off the emergency switchboard when electrically driven (44.3.2).
Paragraph 44.3.3 places every starting, charging, and energy-storage component inside the EDG space solely for operating the EDG. Supplying the emergency air bottle via main or auxiliary compressed-air lines remains permitted provided the check valve sits inside the EDG space.
Fuel fire protection links into revised SOLAS Chapter II-2 Regulation 4.2 (IMO Resolution MSC.99(73), for hulls built from 1 July 2002 onwards). General shipboard oil fuel needs at least a 60 °C closed-cup flashpoint unless otherwise permitted (4.2.1.1). Paragraph 4.2.1.2 permits emergency generators to burn oil fuel down to 43 °C closed-cup, complementing the independent supply of fuel under II-1/42.3.1.1 and 43.3.1.1.
Equally strict is paragraph II-2/4.2.2.3.4 for daily service, settling, or storage oil fuel tanks of 500 litres capacity or greater located above double-bottom tankage. Any oil fuel pipe whose damage would let oil escape must carry a tank-mounted cock or valve. That valve must close safely from outside that compartment during fire (with a special deep-tank tunnel rule where applicable).
The closing sentence of paragraph II-2/4.2.2.3.4 sets a clear layout rule for EDG fuel isolation. Remote operating controls serving the EDG fuel tank valve must sit in a separate location from remote controls for other fuel-tank valves in machinery spaces.
Verify auto-start EDGs built from 1 October 1994 onwards meet SOLAS II-1/44.2 and 44.2.1: at least three consecutive starts with critical-depletion protection (unless a second independent starter exists). Confirm a second source provides three more starts inside 30 minutes unless proven manual starting applies.
Inspect the internal check valve on air-started sets supplied via main or auxiliary air lines, confirm no non-EDG loads draw from starting batteries, accumulators, or air bottles (II-1/44.3.3), and drain receiver moisture under SMS routines.
Test fitted heating arrangements (such as jacket water or room heaters) before cold-weather voyages so engine readiness satisfies SOLAS II-1/44.1.
Trace the tank-mounted EDG fuel quick-closing valve (II-2/4.2.2.3.4 for tanks of 500 litres capacity or greater located above double-bottom tankage) and verify its external remote control sits separately from machinery-space tank controls.
3. IACS 2025 CIC Fleet Data: Eight Deficiency Categories and Nine 'Others' Sub-Findings
From 1 January 2025 through 31 December 2025, IACS (International Association of Classification Societies) ran a global campaign covering shipboard emergency power supply tests following Tokyo MoU concerns over unreliable simulated blackout checks. Released on 5 May 2026 (Rev.1), the report compiles 36,723 vessel inspections across IACS member societies.
Malfunctions were identified on 853 of the 36,723 inspected ships (2.32%), while 35,870 inspected vessels had no identified malfunction. Some vessels logged multiple defects, yielding 995 recorded failure/malfunction deficiencies across eight categories. From its deficiency percentages, IACS excluded 592 port-restriction cases and 69 unexecuted tests caused by cargo work, navigation-gear servicing, engine-room repairs, absent electricians, crew or superintendent refusal over navigation-equipment impact, or non-automatic EDGs backed by an automatic transitional battery.
The IACS report logs these eight category totals without breaking down individual hardware root causes, although Section 4.1(1) names quick-closing valves, control units and EDG starting arrangements as the most critical recurring failures, pointing to maintenance, installation quality or component durability. The category IACS labels 'closing quick-closing valve' ranked first across the fleet with 214 findings (21.51% of the 995 recorded deficiencies).
Malfunction of control units or circuits (described by IACS as PCBs, control relay units, and similar circuits) ranked second with 160 findings (16.08%). In shipboard electrical troubleshooting practice, undervoltage relays, sequence timers, and aged control cards can pass simple panel lamp tests yet fail during a genuine busbar voltage collapse.
Starting arrangement malfunctions ranked third with 136 findings (13.67%), followed in fourth place by wrong engine starting-mode selector switch settings inside the EDG room with 120 findings (12.06%). In service, mis-selected switches (such as panels left on MANUAL or OFF after maintenance) and degraded batteries, chargers, hydraulic starters, or air-start gear can stop automatic cranking altogether.
Malfunctioning air circuit breakers (ACBs) ranked fifth with 116 findings (11.66%), a fault that in practice can block busbar closure or clean interconnector opening. Lack of power supply to essential emergency services ranked sixth with 100 findings (10.05%), followed by prime mover engine malfunctions in seventh with 77 findings (7.74%).
The remaining 72 findings (7.24%) fell under 'Others', where IACS listed nine distinct technical and SMS weaknesses. Hardware findings included unpowered emergency lighting, absent overspeed stops, cooling system failures, fouled filters, air trapped in fuel lines, excess water inside starting air receivers, and low generator insulation resistance.
The 'Others' group also logged crew unfamiliarity alongside missing company or shipboard SMS controlled blackout procedures, risk assessments, and regularly scheduled blackout drills. IACS Section 4.1 highlighted component weaknesses, SMS omissions, and human-factor gaps as core threats to real-blackout readiness.
Target PMS checks on the top five IACS 2025 CIC categories: quick-closing valves (21.51%), control PCBs and relays (16.08%), starting setups (13.67%), wrong selector-switch modes (12.06%), and ACBs (11.66%).
Require a signed post-test entry in the EDG log confirming the mode selector switch stands back in AUTO (where auto-start is fitted) after every local run or maintenance job.
Bleed fuel lines after filter swaps, blow down starting air bottles, inspect cooling paths, and confirm overspeed trip actuation against maker manuals.
Verify essential emergency feeders actually energise during load runs rather than assuming a closed breaker delivers power downstream.
4. Controlled Blackout Testing vs Simulated Sequence Tests Under SOLAS 42.7 and 43.7
SOLAS II-1/42.7 and 43.7 mandate onboard provision to test the complete emergency electrical system periodically, including automatic starting arrangements. In Section 4.1(2) of its 5 May 2026 CIC report, IACS singled out missing controlled blackout SMS procedures across company and shipboard manuals as the notable non-equipment deficiency.
IACS Section 4.1(2) noted that simulated blackout tests using a relay-test switch (RTS) or sequence test are widely used onboard, yet they fail to exercise real blackout circuit paths. As a result, simulated switches give engineers a false sense of emergency readiness.
In marine electrical practice, relying solely on simulation switches can leave hidden defects undetected until main switchboard power disappears. A sticking interconnector auxiliary contact, a drifted main-bus undervoltage relay, an uncharged ACB closing spring, or a mis-wired preferential-trip interlock may only surface during genuine main-supply interruption.
IACS Section 4.2 therefore recommended that ISM audits focus on whether a sufficiently detailed controlled blackout procedure exists in the SMS, and may pay more attention to whether onboard test arrangements demonstrate the emergency power system as a whole, including by controlled blackout testing where appropriate. IACS also said it will consider further analysis of inspection and testing cycles for frequently failing components (quick-closing valves, control units and starting devices), and further studies to standardise design standards for emergency generator simulation tests.
Before executing a controlled blackout test (such as opening the main switchboard interconnector feeding the emergency switchboard), follow the ship's SMS risk assessment and Master's approval. Coordinate with bridge and cargo teams so navigation computers, ECDIS, GMDSS radios, propulsion controls, and cargo plants are safely backed up.
Time the controlled transfer from main supply interruption until the EDG cranks, reaches rated voltage and frequency, closes its ACB, and carries required loads inside the 45-second SOLAS limit (passenger ships, and cargo ships that rely on the generator instead of a transitional source). Confirm automatic interconnector opening (42.5.4 / 43.5.4), non-emergency shedding where necessary (42.5.5 / 43.5.5), and transitional battery hand-off where fitted.
Monitor voltage regulation, frequency stability, cooling fan or louvre operation, lube oil pressure, and exhaust temperature under load per SMS and maker manuals. Restore main supply cleanly as designed and confirm the interconnector recloses. Finish by checking the selector switch stands on AUTO (where auto-start applies), the quick-closing valve stays latched open, and starting sources recharge.
Where the EDG is used exceptionally during lay time in port to feed the main switchboard (unless the Administration instructs otherwise), follow the nine suitable measures in IMO MSC.1/Circ.1572/Rev.2 Section 7 (which consolidates MSC.1/Circ.1464/Rev.1). Those recommendations include a fuel low-level alarm safeguarding statutory endurance, fire detectors in the EDG and switchboard space, and written instructions so that every valve and switch is correctly set for independent emergency operation when the ship is under way.
Audit company and shipboard SMS manuals to confirm a written controlled blackout procedure, risk assessment, and periodic test schedule support SOLAS II-1/42.7 or 43.7.
Never treat an RTS or sequence test alone as complete verification. Prove actual interconnector opening, undervoltage sensing, and ACB closure during approved controlled blackout tests.
Log elapsed start-to-load time (confirming within 45 seconds where applicable), steady voltage, frequency, cooling temperatures, and energised essential feeders.
Execute a two-person restoration sign-off after every run: selector in AUTO (where fitted), fuel quick-closing valve open and unlashed, batteries on float charge, and air or hydraulic starting pressure restored.
The IMO 34th Assembly updated both statutory survey guidelines and Port State Control procedures on 3 December 2025. IMO Resolution A.1207(34) establishes the 2025 HSSC Survey Guidelines (replacing the 2023 edition), while IMO Resolution A.1206(34) establishes the 2025 Procedures for Port State Control (replacing the 2023 edition).
Under A.1207(34) Annex 1, cargo ship Safety Construction (SAFCON) items separate Initial checks strictly from Annual, Intermediate, and Renewal checks. At Initial survey, (CI) 2.1.4.15 verifies dead-ship restart without outside help (II-1/26), (CI) 2.1.4.54 checks the emergency electrical source (II-1/43), and (CI) 2.1.4.55 separately checks EDG starting gear (II-1/44).
At Cargo Annual survey, (CA) 2.2.2.12 re-confirms dead-ship recovery, whereas (CA) 2.2.2.24 merges SOLAS II-1/43 and II-1/44 into one operational check covering starting gear, supplied loads, and automatic operation as far as practicable. Oil, chemical, and gas tankers built from 1 July 2002 onwards also undergo cargo pump-room emergency lighting checks under (CA) 2.2.3.17 (and 2.2.4.1).
Cargo Intermediate (CIn) 2.3.2.1 and Renewal (CR) 2.4.2.1 incorporate all Annual machinery and electrical items without adding extra EDG line items. Oil tankers also test hazardous-zone electrical insulation resistance at Intermediate under (CIn) 2.3.3.3 and at Renewal via (CR) 2.4.3.1 (where maintained recent records may be accepted). Importantly, SAFCON items (CI) 2.1.4.13 and (CA) 2.2.2.10 exclude SOLAS II-2/4.2.2.3.4 remote fuel-tank closing valves.
On cargo ships, functional testing of remote closing oil fuel tank valves sits under the Safety Equipment certificate: Initial (EI) 1.1.4.11, Annual (EA) 1.2.2.12, Periodical (EP) 1.3.2.6, and Renewal (ER) 1.4.2.1. Safety Equipment (EA) 1.2.2.33 verifies muster and embarkation lighting and access routes. Safety Radio items (RI) 4.1.2.6.4, 4.1.2.7.5, 4.1.2.8.1, 4.1.2.9.1, and 4.1.2.11.1 (carried into (RP) 4.2.2.1 and (RR) 4.3.2.1) confirm radio operation on emergency power where fitted.
Passenger Ship Safety surveys (Initial and annual Renewal surveys) keep SOLAS II-1/42 and II-1/44 separate. Initial items (PI) 5.1.3.26 (dead ship), 5.1.3.65 (II-1/42), 5.1.3.66 (II-1/44), 5.1.3.67 (supplementary lighting II-1/42-1), 5.1.3.67.1 (30-minute cabin lighting under II-1/41.6 for hulls built from 1 July 2010 onwards), and 5.1.3.79 (II-2/4.2 remote fuel valves) establish the build baseline. The corresponding checks repeat at each renewal survey under (PR) 5.2.2.30, 61, 62, 63, 64, and 77.
Under IMO Resolution A.1206(34), Appendix 2 Section 5 provides non-exhaustive deficiency examples that may justify detention under the PSCO's professional judgement. SOLAS item 3 names malfunctions of the emergency generator, batteries, switching gear, and emergency lighting, alongside item 1 (propulsion and other essential machinery, and electrical installations), item 6 (quick-closing shut-offs), and item 13 (serious Appendix 7 operational failures).
During hardware checks under Appendix 6, PSCOs treat frayed, disconnected or inoperative quick-closing valve wires and machinery trip mechanisms as signs of poor maintenance (para. 3.2) and investigate power availability for essential and emergency services with tests if an electrical generator stands out of service (para. 3.4). Signs of neglect expand checks to overspeed trips and circuit breakers (para. 3.5). Where a more detailed LRIT inspection is warranted, Appendix 9 para. 3.3.2.1 verifies the LRIT supply from the main and emergency sources, while Appendix 18 para. 2.6.2.7 directs PSCOs to verify that MARPOL Annex VI emergency-only diesel engines (above 130 kW) remain used solely for emergencies.
Operational control under Appendix 7 carries equal emphasis. Part 1 para. 1.2 advises PSCOs against operational tests that, in the Master's judgement, could jeopardise ship, crew, passenger, officer, or cargo safety, while para. 3.1 requires responsible crew to operate essential gear independently. Under Part 1 para. 5.1.4.9, crew unawareness of main and auxiliary engine fuel quick-closing valves may warrant detention consideration. Part 1 para. 5.2.1 cites an engineer unable to demonstrate SOLAS II-2/4.2.2.3.4 fuel oil valves from outside the machinery space as an operational deficiency example related to SOLAS XI-1/4.
Appendix 7 Part 2 para. 1.3.2.1 checks crew familiarity with EDG pre-start preparations (.1), every starting option linked to its energy source (.2), and failed-start procedures (.3). Paragraph 1.3.2.2.2 checks standby generator engine blackout steps, while para. 2.5.4 covers personnel assigned to man emergency generators during fire drills.
Align shipboard survey folders to exact A.1207(34) items: SAFCON (CA) 2.2.2.24 for cargo EDG operation and starting, Safety Equipment (EA) 1.2.2.12 / (EP) 1.3.2.6 for II-2/4.2.2.3.4 quick-closing valves, or Passenger (PR) 5.2.2.61, 62 and 77.
Coach every watchkeeping engineer to perform A.1206(34) Appendix 7 Part 2 para. 1.3.2.1 steps unassisted: pre-start checks, every starting option with its energy source, and failed-start procedures.
Include emergency generator manning in fire drills per A.1206(34) Appendix 7 Part 2 para. 2.5.4, and drill engineers on locating and operating SOLAS II-2/4.2.2.3.4 remote fuel valves from outside the space (Part 1 paras. 5.1.4.9 and 5.2.1).
Keep generator insulation logs, controlled blackout test records, and shipboard records showing MARPOL Annex VI emergency-only engines stay strictly on emergency duty (checked under A.1206(34) Appendix 18 para. 2.6.2.7).
6. Onboard EDG Readiness Walkaround, Troubleshooting and Fleet Engineering Support
SOLAS sets statutory baselines and periodic full-system tests, yet daily dependability rests on disciplined SMS routines and maker maintenance instructions. Treat the walkaround checks and maintenance steps below as shipboard SMS and maker practice supporting SOLAS baselines rather than fixed convention intervals.
Begin every EDG room round at the control panel and switchboard. Confirm the mode selector stands on AUTO (where auto-start is fitted), zero active fault alarms appear, the interconnector shows closed on normal supply, and the ACB closing spring reads charged. During scheduled dead-bus switchboard maintenance, inspect undervoltage and sequence relays for scorched insulation, loose terminals, or vibration wear.
Inspect fuel supply and fire isolation next. Check the day tank level against the fuel needed for 18-hour cargo or 36-hour passenger endurance (or any Administration-approved short-voyage period down to 12 hours). Verify fuel grade meets maker cold-flow limits and the 43 °C closed-cup flashpoint floor, and confirm fuel filters stay clean and air-free.
Examine the tank-mounted quick-closing valve and its separate remote closing control outside the EDG space (where tank capacity is 500 litres or greater above double-bottom tankage). Confirm no temporary pins, lashings, or wedges obstruct the closing arm. Verify pull-wire sheaths or pneumatic actuating pressures match maker limits, and confirm clear labelling in a separate location from machinery-space tank shut-offs.
Check primary and secondary SOLAS II-1/44 starting energy sources (and manual starting gear where relied on). On battery-started sets, verify charger float voltage from the emergency switchboard, clean tight terminals, and cell test records. Confirm starting batteries and chargers sit inside the EDG space solely for EDG operation (II-1/44.3.3), while any Regulation 42 or 43 emergency or transitional batteries sit outside the emergency switchboard space (II-1/42.5.3 or 43.5.3). On hydraulic or air-started backups, verify accumulator pre-charge or bottle pressure, drain moisture condensate, and test the internal check valve on main/auxiliary-fed air sets.
Inspect engine auxiliaries before cranking. Confirm fitted heating arrangements (such as jacket water or room heaters under II-1/44.1) maintain cold-start readiness, and check radiator cores, coolant levels, belts, and ventilation louvres. Verify generator space heaters stay on while stopped to keep winding insulation within maker limits, and test overspeed shutdown per the maker manual during scheduled maintenance.
For EDG trip diagnostics, ACB closing faults, AVR hunting under step loads, or SMS controlled blackout procedure reviews, Marvel Solutionz provides chief-engineer technical consultancy at $350 USD for a 1-hour consultancy (+ 5% sales tax). Fleet teams can also enrol in the LNG, Dual-Fuel & Spark-Gas Academy at $395 USD self-paced (+ 5% sales tax) or Corporate Team Training up to 10 engineers at $3,500 USD (+ 5% sales tax).
Confirm mode selector in AUTO (where auto-start is fitted), ACB spring charged, and zero active panel faults on every routine round, leaving relay terminal checks to scheduled dead-bus maintenance.
Verify the EDG day tank carries full statutory endurance volume, fuel lines are air-free, and the tank-mounted II-2/4.2.2.3.4 quick-closing valve (where capacity is 500 litres or greater) and its separate external remote control move freely.
Test primary and secondary starting sources per shipboard SMS and maker manuals, draining air-receiver condensate and verifying battery charger supply from the emergency switchboard.
Check fitted heaters, cooling radiator and louvres, generator space heaters, winding insulation readings (against maker limits), and overspeed trip readiness before surveys or port calls.
Frequently Asked Questions
Does every SOLAS ship need both a 45-second automatic start EDG and a 30-minute transitional battery?
No. Where an EDG is fitted, passenger ships under SOLAS II-1/42.3.1.2 and 42.3.1.3 must carry both a 45-second automatic full-load EDG and a 30-minute transitional battery. Cargo ships under SOLAS II-1/43.3.1.2 and 43.3.1.3 need either an auto-start EDG carrying required loads inside 45 seconds or a 30-minute transitional battery (and 42.3.2 / 43.3.2 also allow an accumulator battery as the emergency source).
Why did the IACS 2025 CIC warn against relying only on simulated RTS blackout tests?
In its 5 May 2026 report across 36,723 ships (853 vessels logging 995 recorded failure/malfunction deficiencies), IACS stated that simulated RTS or sequence tests fail to exercise real blackout circuit paths and create a false sense of readiness. IACS also flagged missing SMS controlled blackout procedures contrary to SOLAS II-1/42.7 and 43.7.
What dual starting capacity does SOLAS II-1/44 require for ships built from 1 October 1994 onwards?
Under SOLAS II-1/44.2 and 44.2.1 (IMO Resolution MSC.27(61)), automatically started EDGs need Administration-approved starting gear holding energy for at least three consecutive starts, protected against critical depletion from automatic starting unless a second independent starter exists. A second energy source must also deliver three more starts inside 30 minutes unless proven manual starting applies.
What does SOLAS II-2/4.2.2.3.4 require for emergency generator fuel quick-closing valves?
Under SOLAS II-2/4.2.2.3.4 (IMO Resolution MSC.99(73), for hulls built from 1 July 2002 onwards), daily service, settling, or storage fuel tanks of 500 litres capacity or greater above double-bottom tankage need tank-mounted valves on pipes whose damage could release oil. Those valves must close safely from outside the compartment, with remote controls serving the EDG fuel tank sitting separately from machinery-space tank controls. The IACS 2025 CIC category 'closing quick-closing valve' was the largest, at 21.51% (214 of 995) of recorded deficiencies.
What do PSCOs check on emergency generators under IMO Resolution A.1206(34)?
Under A.1206(34), PSCOs may verify crew familiarity with EDG pre-start preparations, each starting option with its energy source, and failed-start procedures (Appendix 7 Part 2 para. 1.3.2.1), standby generator engine blackout steps (1.3.2.2.2), and fire-drill EDG manning (2.5.4). Fuel quick-closing valve awareness (Part 1 para. 5.1.4.9), external SOLAS II-2/4.2.2.3.4 valve demonstration (Part 1 para. 5.2.1), and Appendix 2 non-exhaustive detention examples also apply.
Try the LNG, Dual-Fuel & Spark-Gas simulator free for 5 minutes, then enrol in the Academy: Self-Paced $395 USD or 6-Week Cohort $995 USD (+ 5% sales tax). Or book a 1-hour consultancy for $350 USD (+ 5% sales tax).
Enquiries welcome at any time. Book our daily 1-hour consultation at 12:00 PM Central Time (CT) ($350 USD + 5% sales tax) or send an enquiry about your vessel, power plant or project.
Have an Academy Access Key? Sign in on this page to send comments or questions straight to our instructors.
/guides/emergency-diesel-generator-blackout-start-and-solas-testing-guide/