Marine Sewage Treatment Plant (STP): Aeration Blowers, Biomass Health, Chlorination & MEPC.227(64) MARPOL Annex IV Guide

MARPOL Annex IV, MEPC.227(64), MEPC.157(55), A.1207(34) and A.1206(34) guide to STP aeration blowers, biomass recovery, chlorination and holding tanks.

← All technical guides · Category: Dual-Fuel & Marine Engines · Updated: · 16 min read

Key Takeaways (TL;DR)

  • Revised MARPOL Annex IV (MEPC.115(51)) applies to ships on international voyages of 400 GT and above, and to smaller ships certified for over 15 persons (Reg. 2.1). Under Reg. 9.1 each ship needs a type-approved STP, an approved comminuting and disinfecting system, or a holding tank. A passenger ship under the special area rule may only use an approved STP or a holding tank (Reg. 9.2).
  • IMO Resolution MEPC.227(64), the 2012 STP Guidelines as amended by MEPC.284(70), covers plants fitted from 1 January 2016. Its section 4.1 sets geometric-mean limits for the type-approval test: thermotolerant coliforms 100 per 100 mL, TSS 35 Qi/Qe mg/L, BOD5 without nitrification 25 Qi/Qe mg/L, COD 125 Qi/Qe mg/L, with pH 6 to 8.5 (4.1.4). They are test limits, not a daily sampling duty on board.
  • Where chlorine is the disinfectant, MEPC.227(64) section 5.7 asks the Administration to be satisfied that best technical practice keeps effluent chlorine residual under 0.5 mg/L. Holding-tank sewage may only go overboard at a moderate rate the Administration has approved, with the ship en route at 4 knots or more (Reg. 11.1.1). MEPC.157(55) gives the rate formula.
  • IMO Resolution A.1206(34) Appendix 2 gives four MARPOL Annex IV examples of deficiencies that may warrant detention: no valid ISPP Certificate, an STP without Administration approval and certification, a failed STP, and crew not familiar with the sewage discharge rules.

Marine STP Engine-Room Fault Matrix (MARPOL Annex IV, MEPC.227(64) & MEPC.157(55))

Engine-Room SymptomSubsystemTypical Root CauseVerification & Corrective Action
Septic rotten-egg odour, black liquor, or foaming collapse in aeration chamberAerobic biomass & air diffusersHarsh bleach or caustic cleaners entering black-water drains, failed aeration blower, or plugged fine-bubble air diffusersStop chemical shock entering toilets, switch to holding tank if fitted, restore blower airflow and clean blocked diffusers, and re-seed aerobic culture per the maker manual.
Aeration blower trips on overload or delivers low air pressureRoots or side-channel air blowerBlocked intake air filter, clogged diffuser nozzles raising back-pressure, slipped drive belts, or flooded air check-valveCheck blower suction filter and relief valve, inspect non-return valves on the air manifold to stop sewage back-flooding, verify discharge pressure against maker limits, and switch to standby blower.
High-level alarm in collection or effluent tank, or macerator pump tripsMacerator, discharge pump & level switchesRags, wet wipes, or scale jamming macerator cutters, fouled float switches, or closed overboard discharge valveIsolate power and follow lockout/tagout and biological PPE steps before clearing macerator impellers, clean level probes, confirm overboard valve alignment, and log repairs (MEPC.227(64) section 8).
Floating solids or cloudy discoloured water seen at effluent sample cockSettling hopper & sludge return air-liftPlugged sludge return air-lift line, hydraulic shock from unapproved grey-water flooding, or broken baffle plateVerify MARPOL Annex IV Reg. 11.1.2 compliance (no visible floating solids or surrounding water discolouration), clear the return air-lift jet, check inlet buffering, and divert to holding tank until clear.
Zero chlorine residual or excessive chlorine smell at discharge sample pointChlorinator tablet tube or dosing pumpBridged or empty calcium hypochlorite tablets, air-locked dosing pump, fouled contact tank, or overdosed chemical pumpClear bridged tablet cartridges safely with PPE, check dosing pump priming and the injection check-valve, test residual chlorine against the maker's set-points, and adjust the feed. Type approval expects residual chlorine under 0.5 mg/L (MEPC.227(64) section 5.7).
Shore reception hose will not mate or holding-tank gauge is unreadableStandard discharge flange & holding tankMissing or corroded MARPOL Annex IV Reg. 10 flange, seized overboard valve, or fouled tank sight glassCheck the Reg. 10.1 flange (210 mm outside diameter, 170 mm bolt circle, four 18 mm slotted holes, 16 mm thick, four 16 mm bolts) and restore a working visual contents indicator on the holding tank (Reg. 9.1.3).

1. MARPOL Annex IV Scope, Equipment Options & Standard Discharge Flange

Revised MARPOL Annex IV, adopted by IMO Resolution MEPC.115(51), has been in force since 1 August 2005. Under Regulation 2.1 it applies to ships on international voyages of 400 GT and above, and to smaller ships certified for over 15 persons. Existing ships came in five years after the Annex entered into force. Existing ships with keels laid before 2 October 1983 must, as far as practicable, be equipped so their sewage discharges can meet Regulation 11 (Reg. 2.2). A ship trading to ports or offshore terminals of other Parties gets an International Sewage Pollution Prevention (ISPP) Certificate under Regulation 5, after a survey under Regulation 4.

Regulation 9.1 gives three equipment options. A ship may fit an STP type-approved against the IMO standards (Reg. 9.1.1). It may instead fit an approved comminuting and disinfecting system, with temporary storage for use when it is less than 3 nm from the nearest land (Reg. 9.1.2). The third option is a holding tank sized for the ship's trade and the number of people on board, with a visual contents indicator (Reg. 9.1.3). Regulation 9.2, added by MEPC.200(62), limits a passenger ship that falls under the special area rule in Regulation 11.3 to an approved STP or a holding tank.

Regulation 11.1, as replaced by MEPC.200(62), covers all non-passenger ships in any sea area, and passenger ships outside special areas. An operating STP that the Administration has certified to the Regulation 9.1.1 standards may discharge, provided the effluent shows no visible floating solids and does not discolour the water around it (Reg. 11.1.2). Comminuted and disinfected sewage from an approved system may go overboard more than 3 nm from the nearest land. Untreated sewage may go overboard only more than 12 nm out (Reg. 11.1.1). 'Nearest land' is measured from the territorial sea baseline (Reg. 1.5). Sewage stored in holding tanks, and sewage from spaces holding live animals (added by MEPC.164(56)), must never be dumped at once. It goes out at a moderate rate that the Administration has approved, with the ship en route at 4 knots or more.

Under Regulation 10.1, the ship's sewage discharge pipeline and the reception facility's pipe both need a standard discharge connection. Ships in dedicated trades, such as passenger ferries, may use another connection the Administration accepts, for example a quick coupling (Reg. 10.2). The flange is flat-faced, of steel or an equivalent material, and takes pipes up to 100 mm bore. With a suitable gasket it must suit a 600 kPa service pressure. Its dimensions are in the fault table and the FAQ.

Regulation 3 gives two narrow exceptions to Regulation 11. They are separate from Regulation 11.2, which lets a State apply less strict rules in its own waters. The first exception is a discharge needed to keep the ship and its people safe or to save life at sea (Reg. 3.1.1). The second is a discharge caused by damage to the ship or to its equipment, but only if all reasonable precautions were taken before and after the damage to prevent or reduce it (Reg. 3.1.2). Do not count on Regulation 3 to cover a plant you knew was failing. Keep holding capacity and the shore connection ready instead.

Some coastal States and ports set stricter rules in their own waters, including no-discharge zones. Check the local port rules and your Safety Management System before opening any treated-effluent overboard valve in port, estuaries or coastal waterways, and keep those valves labelled and locked or logged.

  • Confirm the ISPP Certificate shows the installed STP type, maker and the effluent standard it is certified to (or the holding-tank capacity and location). Check it matches the copy of the STP type approval certificate kept on board (MARPOL Annex IV Reg. 5 and the certificate form in its Appendix; MEPC.227(64) annex).
  • Check the holding tank's visual contents indicator works (MARPOL Annex IV Reg. 9.1.3), and test any high-level alarm the maker fitted.
  • Inspect the MARPOL Annex IV Regulation 10 shore discharge flange (210 mm OD, 170 mm bolt circle, four 18 mm slotted holes, 16 mm thick). Keep four 16 mm bolts, nuts and a clean gasket ready.
  • Confirm overboard sewage valve lock-out logs and port-limits changeover procedures match the vessel's SMS.

2. MEPC.227(64) vs MEPC.159(55) Effluent Standards & Passenger Special Areas

IMO guidance for STP type approval has had three versions: Resolution MEPC.2(VI) (1976), the 2006 Revised Guidelines in Resolution MEPC.159(55), and the 2012 Guidelines in Resolution MEPC.227(64), later amended by MEPC.284(70). Under MEPC.227(64) section 1.2.2, the 2012 standards (except section 4.2) apply to STPs fitted from 1 January 2016 on all non-passenger ships, and on passenger ships outside special areas. MEPC.284(70) added section 1.2.2.3 to say what counts as fitted from that date. It covers ships whose keels were laid on or after it. For other ships it counts from the date in the plant's delivery contract or, if there is none, from the date the plant actually arrives on board.

Older plants follow the version in force when they were fitted. MEPC.159(55) section 1.3 applies it to plants installed from 1 January 2010. MEPC.227(64) sections 1.2.4 and 1.2.5 keep MEPC.159(55) for plants fitted from 1 January 2010 to the end of 2015, and MEPC.2(VI) for plants fitted before 2010. Both paragraphs leave out passenger ships that discharge treated sewage in a special area.

MEPC.227(64) changed the test standards in two main ways: it compensates for dilution, and it measures BOD5 without nitrification. Section 3.2 says an approved STP should not meet the standards by dilution alone. Where dilution water (section 2.3) is essential to the process, the mg/L limits are scaled by Qi/Qe, the influent flow divided by the effluent flow. MEPC.159(55) used fixed mg/L limits and plain BOD5.

Section 4.1 of MEPC.227(64) sets these geometric-mean limits for the type-approval test. Thermotolerant coliforms: 100 per 100 mL (4.1.1). Total suspended solids: 35 Qi/Qe mg/L when tested ashore, or up to (35 + x) Qi/Qe mg/L when tested on board, where x allows for solids in the flushing water (4.1.2). BOD5 without nitrification: 25 Qi/Qe mg/L by ISO 5815-1:2003 or an equivalent. COD: 125 Qi/Qe mg/L by ISO 15705:2002 or an equivalent (4.1.3). Effluent pH during the test should stay between 6 and 8.5 (4.1.4). These are the figures the plant proved at type approval. They are not a daily sampling duty on board, but they show what a healthy plant can do.

Passenger ships that want to discharge treated sewage in an Annex IV special area must also meet nutrient limits. MEPC.200(62) added the special area rules and named the Baltic Sea. MEPC.274(69) set the earliest dates for the Regulation 11.3 ban, and MEPC.275(69) fixed the Baltic dates: new passenger ships from 1 June 2019 and other existing passenger ships from 1 June 2021. Existing passenger ships sailing directly between a port outside the Baltic and a port east of 28°10′ E inside it, with no other Baltic port calls, follow from 1 June 2023. Under MEPC.227(64) section 4.2, total nitrogen should stay at or under 20 Qi/Qe mg/L; otherwise the plant should cut the nitrogen load by at least 70%. Total phosphorus should stay at or under 1.0 Qi/Qe mg/L; otherwise its load should fall by at least 80%.

Under MEPC.227(64) as amended by MEPC.284(70), the type approval certificate has two forms: Annex 1 includes section 4.2 and Annex 2 leaves it out. Both record the designed hydraulic loading (m3/day) and the organic loading as BOD5 without nitrification (kg/day). The appendix records the disinfectant used and whether grey water was added in the test. A vacuum toilet system uses less flush water than a gravity one, so the plant receives a stronger mix (section 5.2.1 asks the shore test to allow for this). Check that the total daily inflow stays inside the rated hydraulic and organic loads.

  • Confirm which IMO guideline generation (MEPC.227(64), MEPC.159(55), or MEPC.2(VI)) matches the installation date on the ship's ISPP Certificate and STP Type Approval Certificate.
  • Check designed hydraulic loading (m3/day) and organic BOD5 without nitrification loading (kg/day) on the Type Approval Certificate whenever extra riding crew or shipyard contractors board.
  • On passenger ships that discharge treated sewage inside a special area, check the type approval certificate is the Annex 1 form that includes the section 4.2 nutrient standards (MEPC.227(64) as amended by MEPC.284(70)).
  • Keep effluent sampling cocks clean and accessible so visual discharge checks can confirm zero visible floating solids or discolouration (MARPOL Annex IV Reg. 11.1.2).

3. Biological STP Diagnostics: Aeration Blowers, Diffusers & Biomass Health

Biological aerobic STPs rely on live micro-organisms, suspended in aerated liquor or growing on fixed media, to break organic waste down into carbon dioxide, water and settleable sludge. Electro-chemical and physical-chemical plants work differently and rely on filtration or chemical oxidation. A membrane bioreactor is still a biological plant. Any biological unit loses treatment quickly if dissolved oxygen falls or toxic chemicals kill the bacteria.

Aeration blowers keep a biological plant alive. A plant may have duty and standby side-channel or rotary positive-displacement blowers feeding submerged fine-bubble diffusers or air-lift pipes. Inspect suction filters, compare blower discharge pressure and motor current with the maker's manual, and check belt tension on belt-driven units. Watch for a hidden failure: a leaking non-return valve on the air header can let sewage flood back into a stopped standby blower.

Rising blower discharge pressure with weak surface bubbling points to scaled or slimed diffuser membranes. Violent boiling in one corner with low header pressure points to a broken air pipe or a burst diffuser, which leaves dead corners where sludge turns septic. Follow the maker's tank-emptying, gas-freeing and enclosed-space entry steps before opening any chamber to change diffusers.

Chemical shock is a typical cause of sudden biological collapse. Strong chlorine bleach, acid descalers, phenolic disinfectants or oily rags flushed down accommodation toilets can kill the aerobic bacteria quickly. Once the colony dies, the liquor turns from earthy brown to dark grey or black, smells of hydrogen sulphide and stops settling cleanly in the clarifier hopper.

Accommodation housekeeping matters as much as engine-room hardware. Agree with the chief steward and the deck department that only cleaning products the plant maker accepts reach the black-water lines. MEPC.227(64) section 5.9.5 invites Administrations to ask makers to list suitable chemicals in the manual, so use that list where it exists. Also confirm laundry and galley grey water is routed as the approved piping diagram shows. Unplanned detergent or hot grease can wash biomass out of the settling chamber.

When recovering a poisoned or freshly cleaned biological plant, follow the maker's start-up protocol carefully. Flush out toxic liquor to a holding tank or approved reception facility, refill with clean water per maker instructions, run continuous aeration, and dose maker-approved biological starter culture if specified. Monitor sludge settling in a clear measuring jar per the maker manual so you spot healthy floc formation before resuming overboard treated discharge.

  • Log duty and standby aeration blower discharge pressure, amperage, and changeover intervals during routine engine-room watches.
  • Check air-header non-return valves and pressure-relief valves so sewage cannot siphon back into a stopped blower.
  • Audit accommodation and galley toilet-cleaning products to confirm only maker-compatible, non-biocidal cleaners enter black-water drains.
  • Perform visual effluent clarity and sludge-settling jar checks per the maker manual to detect biomass loss before visible solids escape overboard.

4. Macerators, Settling Hoppers, Sludge Return & Disinfection Residual Control

Downstream of aeration, a settling chamber separates clear treated liquid from heavier biological floc. Clear effluent overflows a weir into the disinfection tank while settled sludge slides down sloped hopper walls and is lifted continuously back into the aeration chamber by an air-lift ejector or return pump. If that return air-lift clogs with paper fibre or grease, sludge piles up in the clarifier, turns anaerobic, and floats upward into the effluent tank as dark mats.

Check sludge-return sight glasses or discharge spouts on your engine-room rounds. A short burst of service air or flushing water through the maker's clearing connection frees a plugged air-lift before carry-over reaches the disinfection chamber. Also check the skimmer returns, because a clogged skimmer leaves a grease crust on the settling surface.

Inlet macerator pumps and effluent discharge pumps face tough mechanical abuse from wet wipes, cotton swabs, and scale chips breaking loose from vacuum toilet piping. Repeated thermal overload trips or high pump vibration signal jammed cutters, worn mechanical seals, or fouled check-valves. Before dismantling any sewage pump, isolate electrical power, close suction and discharge valves, wear full splash protection and gloves, and ventilate the work area thoroughly against sewer gas.

Disinfection is the last stage, aimed at keeping thermotolerant coliforms within the 100 per 100 mL test standard (MEPC.227(64) section 4.1.1). Section 5.7 points to the environmental harm from disinfectant residues and by-products, for example from chlorine. It recommends that Administrations encourage ozone, ultraviolet light or other disinfectants with less impact. Where chlorine is used, the Administration needs to be satisfied that best technical practice keeps effluent chlorine residual under 0.5 mg/L. On board, follow the maker's dosing settings and test the residual as the manual says.

On tablet-fed chlorinators, calcium hypochlorite tablets absorb humidity in warm engine rooms, then swell and bridge inside the feed tube so no chlorine reaches the contact tank. Crumbled tablet sludge on the base screen can do the opposite and push residual chlorine above 0.5 mg/L. Keep tablet tubes dry, use only the tablets the maker specifies (never pool tablets of unknown make-up), and never mix chlorine products that can react violently together.

On liquid sodium hypochlorite dosing plants or UV-disinfected STPs, inspect dosing pump diaphragms, foot valves, injection quills and dechlorination units (where fitted) as your planned maintenance says. On UV sewage modules, clean the quartz sleeves as the maker's manual says, because turbid effluent coats the glass and blocks the UV light. Where chlorine is used, test residual chlorine at the sample point as the manual says, so disinfection works while the residual stays under 0.5 mg/L.

  • Check sludge-return air-lift and surface-skimmer flow visually during routine engine-room rounds per the maker manual so settled sludge does not turn septic and carry over.
  • Inspect macerator cutters, discharge pump seals, and level floats per the maker manual, applying lockout/tagout and sewer-gas precautions before opening casings.
  • Keep calcium hypochlorite tablet tubes clean and dry, stock only maker-approved tablets, and check liquid dosing pumps for air-locking.
  • Where chlorine disinfection is fitted, test effluent residual as the maker's manual says and keep it under 0.5 mg/L (MEPC.227(64) section 5.7).

5. Sewage Holding Tanks, MEPC.157(55) Discharge Rates & Hydrogen Sulphide Safety

Ships that rely on a holding tank under Regulation 9.1.3, or that divert sewage to one in port and during STP maintenance, must manage its discharge with care. Section 1 above sets out the Regulation 11.1.1 distance, speed and moderate-rate rules. Passenger ships under the special area rule (Reg. 11.3) may not discharge untreated sewage in the special area at all.

IMO Resolution MEPC.157(55) gives the standard for approving and calculating that moderate rate. Its section 1.2 says the rate applies to untreated sewage stored in holding tanks. Section 3.1 sets the maximum rate at 1/200,000 of the swept volume: DRmax = 0.00926 × V × D × B (m3/h). V is the ship's average speed in knots, D the draught in metres and B the breadth in metres. Under section 3.2, DRmax is the average over any 24 hours, or over the discharge period if shorter. Hourly rates may exceed it by no more than 20%.

Watch for lower draught and speed on ballast passages, because both reduce the permitted rate. MEPC.157(55) section 4.1 bases the main approved rate on the maximum summer draught and maximum service speed. The Administration may also approve secondary rates for other draught and speed combinations. Section 5.2 lets a fixed-rate pump be set for the rate allowed at 4 knots, or for a stated minimum speed above 4 knots. If the planned flow is more than the 4-knot rate allows, cut the flow or raise the speed. The approval states both the rate and the speed (section 5.3).

Before discharging untreated holding-tank sewage, MEPC.157(55) section 6.1 says the person in charge of sewage operations should check three things. The ship must be en route, more than 12 nm from the nearest land, and at a speed that matches the approved rate. Ships with large discharge needs should consider keeping notes of their discharge calculations to show compliance.

Holding tanks also bring gas and structural hazards. Stagnant untreated sewage gives off toxic hydrogen sulphide (H2S), methane and carbon dioxide, and uses up oxygen. Keep tank vents and flame screens clear, and run any holding-tank aeration or mixing lines as the maker says to limit septic build-up. Before opening or entering a sewage tank or STP compartment, follow IMO Resolution MSC.581(110) on enclosed space entry and your SMS: risk assessment, atmosphere testing, ventilation and an entry permit.

Regulation 9.1.3 requires a visual means of showing how much the holding tank holds. Under IMO Resolution A.1207(34), the initial ISPP survey checks that the tank was built satisfactorily and has that indicator ((SI) 3.1.2.2). The renewal survey examines the system externally and confirms, as far as practicable, that it works ((SR) 3.2.2.2). It checks that a procedure for discharging animal effluent is in place ((SR) 3.2.2.3). Where a holding tank is the ship's sewage system, it also checks that a discharge rate approval is on board ((SR) 3.2.2.4). Check sight glasses, level sensors and any high-level alarms to help prevent overflows.

  • Keep the Administration's approved MEPC.157(55) discharge rate (DRmax = 0.00926 × V × D × B), and any secondary rates for other draughts and speeds, at the sewage pump controls.
  • For non-passenger ships (and passenger ships outside Special Areas), verify distance exceeds 12 nm from the nearest land, speed is at least 4 knots, and pump flow stays within approved limits before discharging untreated holding-tank sewage (Reg. 11.1.1).
  • Keep holding-tank vent lines clear. Before any sewage tank entry, follow IMO Resolution MSC.581(110) and your SMS: gas testing, ventilation and an entry permit.
  • Test the holding tank's visual contents indicator (MARPOL Annex IV Reg. 9.1.3) and any high-level alarm as your planned maintenance says, so the spare capacity is known.

6. HSSC ISPP Surveys (A.1207(34)), PSC Detention Grounds (A.1206(34)) & Records

Statutory surveys of sewage equipment follow MARPOL Annex IV Regulation 4, with IMO Resolution A.1207(34) (the HSSC Survey Guidelines, 2025, Annex 3 part (S)) as guidance. At the initial survey, the plan review ((SI) 3.1.1) checks the arrangements for the STP, comminuting system or holding tank, and the type approval or tank capacity. The inspection after installation ((SI) 3.1.2) checks the plant externally and confirms it works. Surveyors also confirm the holding tank's construction and visual indicator, the Regulation 10 standard connection and the pipeline to a reception facility.

The ISPP Certificate has a renewal survey at intervals of up to five years, not annual surveys (Annex IV Reg. 4.1). Under A.1207(34) (SR) 3.2.2, the renewal survey confirms that no change or new equipment affects the certificate (Annex IV Reg. 4.8). It examines the system externally and confirms, as far as practicable, that it works (Reg. 9). MEPC.227(64) section 6 asks Administrations, at renewal and additional surveys (Regs. 4.1.2 and 4.1.3), to try to make sure the STP still performs to the Regulation 4.1.1 conditions. Under section 8, the maker should set out routine maintenance in the manuals, and every routine job and repair should be logged.

Crew familiarisation also matters. MEPC.227(64) section 7 notes that familiarisation sits under the ISM Code Safety Management System. It reminds Administrations that crew training should cover how to run and maintain the STP. Engineers and deck officers on watch should both know the discharge distances (3 nm and 12 nm from the nearest land), plus the 4-knot minimum speed for holding-tank discharge. They should also know the overboard valve rules in port and the emergency steps if the STP fails.

PSC inspections under MARPOL Annex IV Regulation 14 and IMO Resolution A.1206(34) include checking the ISPP Certificate (Appendix 12, Part A, item 14) as well as operational compliance. A.1206(34) Appendix 2 gives four MARPOL Annex IV examples of deficiencies that may warrant detention. They are no valid ISPP Certificate, an STP without Administration approval and certification, a failed STP, and crew not familiar with the sewage disposal and discharge rules.

Under A.1206(34) Appendix 7, Part 2 paragraph 1.9 lets the inspector check whether the STP, comminuting system or holding tank was used, and record any claimed inadequacy. It also lets the inspector check that the crew know how to operate it. Part 1 paragraph 5.2 gives, as an example deficiency, an engineer officer who cannot show how the STP works. A pre-arrival walk-round (see the checklist below) helps avoid survey remarks and PSC findings.

When persistent biological washout, high effluent turbidity, blower failures, or ISPP survey questions disrupt engine-room operations, Marvel Solutionz offers direct technical support. Senior marine engineering troubleshooting is available at $350 USD for a 1-hour consultancy (+ 5% sales tax). For structured engineering upskilling, the LNG, DF & SG Academy is $395 USD self-paced (+ 5% sales tax), and Corporate Team Training for up to 10 engineers is $3,500 USD (+ 5% sales tax).

  • Keep dated records of all routine STP servicing and repairs, following the maker's manual (MEPC.227(64) section 8). Have them ready for renewal and additional ISPP surveys (MARPOL Annex IV Regs. 4.1.2 and 4.1.3; A.1207(34) General 4.7 and Annex 3 part (S) (SR) 3.2).
  • Walk down the STP before arrival: confirm blower running, clarifier surface clear, effluent sample free of visible floating solids or discolouration, and disinfectant stocked (where fitted).
  • Brief junior engineers and bridge officers on MARPOL Annex IV Regulation 11 discharge distances and holding-tank rates (A.1206(34) Appendix 2 and Appendix 7), plus SMS port zero-discharge valve locks.
  • Confirm the ISPP Certificate, STP Type Approval Certificate copy (with Appendix), and maker operating and maintenance manual sit together in the statutory file.

Frequently Asked Questions

What are the MEPC.227(64) effluent standards for a marine sewage treatment plant?

Section 4.1 sets geometric-mean limits for the type-approval test of plants fitted from 1 January 2016. They are: thermotolerant coliforms 100 per 100 mL, TSS 35 Qi/Qe mg/L (ashore), BOD5 without nitrification 25 Qi/Qe mg/L, COD 125 Qi/Qe mg/L, pH 6 to 8.5. MEPC.284(70) amended the Guidelines. Passenger ships that discharge in a special area also need the section 4.2 nutrient limits.

What residual chlorine figure applies to STP effluent under MEPC.227(64)?

Section 5.7 recommends that Administrations encourage ozone, UV or other lower-impact disinfectants. Where chlorine or a chlorine compound is used, the Administration needs to be satisfied that best technical practice keeps effluent chlorine residual under 0.5 mg/L. It is a type-approval guideline. On board, follow the maker's dosing and test instructions.

How is the maximum untreated sewage holding-tank discharge rate calculated?

Outside the special area rules for passenger ships (Reg. 11.3), Regulation 11.1.1 allows it only more than 12 nm from the nearest land, en route at 4 knots or more, at the approved moderate rate. MEPC.157(55) section 3.1 gives DRmax = 0.00926 × V × D × B (m3/h) as a 24-hour average. Hourly rates may run up to 20% above it (section 3.2).

What MARPOL Annex IV deficiencies may warrant PSC detention under IMO Resolution A.1206(34)?

IMO Resolution A.1206(34) Appendix 2 gives four MARPOL Annex IV examples that may warrant detention: no valid ISPP Certificate, an STP without Administration approval and certification, a failed STP, and crew not familiar with the sewage disposal and discharge rules.

What are the MARPOL Annex IV Regulation 10 standard discharge connection dimensions?

Regulation 10.1 sets a flat-faced flange of 210 mm outside diameter and 16 mm thickness, with four 18 mm slotted holes on a 170 mm bolt circle and four 16 mm bolts and nuts.

Regulatory & Technical Sources

Train with Marvel Solutionz or get expert help

Try the LNG, Dual-Fuel & Spark-Gas simulator free for 5 minutes, then enrol in the Academy: Self-Paced $395 USD or 6-Week Cohort $995 USD (+ 5% sales tax). Or book a 1-hour consultancy for $350 USD (+ 5% sales tax).