SOLAS II-2/10.5.6 (MSC.99(73)) requires an approved local-application water-based (or equivalent) fixed fire system in Category A machinery spaces above 500 m³. Coverage applies to passenger ships of 500 GT or above and cargo ships of 2,000 GT or above built on or after 1 July 2002. MSC.338(91) widened internal combustion scope for ships built on or after 1 July 2014.
This installation supplements the main fixed system (such as CO2, high-expansion foam, or FSS Ch. 7 water-spraying). It protects areas such as fire-hazard parts of internal combustion machinery, boiler fronts, fire-hazard parts of incinerators, and purifiers for heated fuel oil without stopping engines, evacuating personnel, or closing off the space.
IMO guidance MSC.1/Circ.1387 (with Corr.1 and UI Circ.1276/Rev.2) advises a supply that is ready at once and lasts at least 20 minutes. It is sized for the one section needing the most water, not several sections at once (3.2.4 and 3.3.1). Periodically unattended spaces use two approved flame detectors, one approved flame plus one approved smoke detector, or another Administration-accepted arrangement (3.1.5.2).
Under SOLAS II-2/14.2 and IMO guidelines Circ.1432 / Circ.1516, crews test header-tank and pump-unit water quality quarterly (6.5) and blow dry-pipe headers annually (7.5.12). Open-head installations flow at least one section yearly (all within 5 years, 7.5.16), valves undergo internal inspection every 5 years (9.3.2), and pressure cylinders hydrotest and undergo internal examination every 10 years (10.2).
MSC.403(96) (effective 1 January 2020) replaced FSS Code Ch. 8 paragraph 2.4.1 for accommodation, control-station, and service-space automatic sprinklers and added Chapter 17, making zero edits to FSS Ch. 7 or SOLAS II-2/10.5.6. Under HSSC A.1207(34) and PSC A.1206(34), blocked headers, faulty alarms, or operator unfamiliarity may trigger survey findings or warrant detention.
Local-Application Water-Mist (SOLAS II-2/10.5.6 & Circ.1387) vs Main Fixed Water Systems (FSS Ch. 7)
Passenger ships of 500 GT or above, plus cargo ships of 2,000 GT or above, with Category A spaces above 500 m³ (built on or after 1 July 2002, II-2/1.1 & 10.5.6.1 to 10.5.6.2).
Category A machinery spaces (10.5.1.1, 10.5.2.1, unattended steam of 375 kW and above under 10.5.3.1) and tanker cargo pump-rooms (10.9.1.3) using fixed water-spraying or equivalent mist.
Statutory SOLAS II-2/10.5.6.1 to 10.5.6.2. Pre-July 2002 passenger ships of 2,000 GT or above complied by 1 October 2005 at the latest (II-2/1.2.2.4).
Protected equipment
Areas such as fire-hazard parts of internal combustion machinery (ships built on or after 1 July 2014 via MSC.338(91)), boiler fronts, incinerator fire hazards, and purifiers for heated fuel oil (10.5.6.3).
Nozzles placed above bilges, tank tops, fuel-oil spread zones, and specific machinery hazards (FSS 7/2.1.2.1) delivering an effective average rate at 5 L/m²/min minimum or higher per Administration (7/2.1.1.2).
Statutory SOLAS II-2/10.5.6.3. Where 10.5.6 applies to ships built before 1 July 2014, 10.5.6.3.1 covers main-propulsion and power-generation internal combustion machinery.
Water reserve & sizing
Immediate fresh or sea water supply for at least 20 min covering the single section requiring the greatest volume (Circ.1387 2.4, 3.2.4 & 3.3.1). Multi-engine spaces divide into 2 or more separate sections (3.2.4).
Fixed pressure pump sited outside the protected space(s) and sized to supply all sections in any single protected compartment simultaneously at required pressure (FSS 7/2.1.1.4 & 2.1.2.3).
Recommendatory IMO guidance MSC.1/Circ.1387 (2.4, 3.2.4, 3.3.1 & 3.3.5) vs mandatory FSS Code Ch. 7 (2.1 and 2.2).
Release & detection
Periodically unattended spaces fit automatic release alongside manual activation. Continuously manned spaces require manual release only (10.5.6.2). Auto uses 2 approved flame, 1 approved flame + 1 approved smoke, or Administration-accepted detectors (Circ.1387 3.1.5.2).
Section distribution valves and pump controls sit outside the protected room (FSS 7/2.1.2.2, 7/2.1.2.3), kept charged at required pressure with automatic pump start on pressure drop (FSS 7/2.1.3).
Statutory release split in II-2/10.5.6.2 and activation alarms in 10.5.6.4. Automatic detector pairing is recommendatory IMO guidance (Circ.1387 3.1.5).
Nozzle layout & water quality
UI Circ.1276/Rev.2 Sketches 1.1 to 1.5 illustrate outer-nozzle placement (at least D/4 outside or at/outside the edge) and D/2 by D/2 single-nozzle coverage. Circ.1432 sets annual open-head flow (7.5.16), while Circ.1516 adds quarterly tank/pump water-quality checks (6.5).
FSS 7/2.1.1.3 mandates precautions against nozzle clogging by impurities or corrosion. MSC.403(96) replaced FSS Ch. 8 para. 2.4.1 (2.4.1.1 to 2.4.1.2) for accommodation, control-station, and service-space sprinklers and added Chapter 17.
Recommendatory IMO UI Circ.1276/Rev.2 (guidance for ships contracted on or after 4 Dec 2024) and IMO guidelines Circ.1432 / Circ.1516 under SOLAS II-2/14.2.
Pipe blow-through & survey
Annual dry air or nitrogen blow-through of dry headers (Circ.1432 7.5.12), zero 2-year tasks (Sec. 8), 5-year internal valve inspections (9.3.2), and 10-year cylinder hydrotests and internal exams (10.2).
Same Circ.1432 / Circ.1516 maintenance framework plus HSSC periodical item (EP) 1.3.2.2 (A.1207(34)), which checks that the fixed system's distribution pipework has been shown to be clear.
Statutory SOLAS II-2/14.2.2 maintenance plan, HSSC A.1207(34) machinery items, and PSC A.1206(34) App. 2 Sec. 5 SOLAS Item 6.
Engine-room local-application water-mist systems (water-based local-application systems, sometimes shortened to FWBLAFFS) take their statutory mandate from SOLAS Chapter II-2 Regulation 10.5.6, adopted under IMO Resolution MSC.99(73) (5 December 2000, effective 1 July 2002). Under SOLAS II-2/1.1, this rule governs ships built on or after 1 July 2002. Regulation 10.5.6 has four paragraphs, 10.5.6.1 to 10.5.6.4. For ships built before 1 July 2002, SOLAS II-2/1.2.2.4 applied it only to passenger ships of 2,000 GT or above, with a compliance date no later than 1 October 2005.
Under regulation 10.5.6.1, coverage applies to passenger ships of 500 GT or above, plus cargo ships of 2,000 GT or above. Under 10.5.6.2, Category A spaces above 500 m³ in volume must fit an approved local-application water-based (or equivalent) fixed fire system based on IMO guidelines. That installation supplements the main fixed extinguishing plant required by 10.5.1.1 and never replaces fixed gas, high-expansion foam, or pressure water-spraying / equivalent mist protection (10.4.1.1).
Release controls depend on watchkeeping mode under 10.5.6.2. Periodically unattended Category A spaces must fit automatic release alongside manual activation, whereas continuously manned spaces are only required to carry manual release. Subparagraph 10.5.6.3 specifies that local-application nozzles protect specific machinery areas without stopping engines, evacuating personnel, or closing off the space.
IMO Resolution MSC.338(91) (adopted 30 November 2012, effective 1 July 2014) widened subparagraph 10.5.6.3.1. Ships built on or after 1 July 2014 must protect areas such as fire-hazard parts of internal combustion machinery. Where 10.5.6 applies to earlier builds, 10.5.6.3.1 covers main-propulsion and power-generation internal combustion machinery. Boiler fronts (10.5.6.3.2), fire-hazard parts of incinerators (10.5.6.3.3), and purifiers for heated fuel oil (10.5.6.3.4) remain protected targets across both build eras.
Under 10.5.6.4, activation must trigger a visual alarm and a distinct sound alarm, both in the space being protected and at every station that is always manned. The alarm must show which system has operated. Those alarms supplement fire detection systems required elsewhere in SOLAS Chapter II-2, including II-2/7.4 for periodically unattended or remotely controlled machinery spaces. On passenger ships built on or after 1 July 2010, SOLAS II-2/23.6 (MSC.216(82) Annex 3, adopted 8 December 2006) requires full safety-centre functionality covering operation, control, and/or monitoring. Those lines span local-application systems (.11), sprinkler and equivalent systems (.12), and machinery-space water-based extinguishing installations (.13).
Chief engineers must keep FSS Code Chapters 7 and 8 separate from regulation 10.5.6. FSS Code Chapter 7 (MSC.98(73)) sets mandatory standards for main fixed pressure water-spraying systems and equivalent water-mist plants (7/2.2). Those cover Category A spaces (10.5.1.1, 10.5.2.1, unattended steam of 375 kW and above under 10.5.3.1) and tanker cargo pump-rooms (10.9.1.3). Under FSS 7/2.1, nozzles protect bilges, tank tops, fuel-oil spread zones, and machinery hazards (7/2.1.2.1) at 5 L/m²/min minimum effective average distribution or higher per Administration (7/2.1.1.2). Safeguards against clogging sit in 7/2.1.1.3, pumps supply all sections in any single protected compartment simultaneously (7/2.1.1.4), controls sit outside (7/2.1.2.2, 7/2.1.2.3), and pumps auto-start on pressure drop (7/2.1.3). IMO Resolution MSC.403(96) (adopted 19 May 2016, effective 1 January 2020) replaced FSS Code Chapter 8 paragraph 2.4.1 with 2.4.1.1 (freeze protection) and new 2.4.1.2. Paragraph 2.4.1.2 asks for special attention to the maker's water-quality specification, so that sprinkler heads do not corrode or clog. MSC.403(96) also added Chapter 17 on helicopter facility foam. It made zero edits to FSS Chapter 7 or SOLAS II-2/10.5.6.
Detailed approval engineering criteria appear in IMO circular MSC.1/Circ.1387 (issued 10 December 2010 following MSC 88) and corrigendum MSC.1/Circ.1387/Corr.1 (issued 8 September 2022). Both texts are recommendatory IMO guidelines using advisory wording rather than statutory mandates, applied during flag-State or recognised-organisation plan approval. Circular 1387 replaced MSC/Circ.913 while permitting earlier Circ.913 test reports for approvals and noting compliant Circ.913 installations may stay in active shipboard service.
Corrigendum 1 (8 September 2022) replaced Appendix figures 3.4.2.4 to 3.4.2.6, the drawings for single rows of nozzles and single nozzles. Those figures show the D/2 coverage of one nozzle and the D/4 extension of outer nozzles. Appendix 3.4.2.4 notes that the fuel spray positions drawn in them are for information only.
Check water reserve sizing carefully during engine-room audits. Under Circ.1387 paragraphs 2.4 and 3.3.1, the system should stand ready for immediate use and supply fresh or sea water (plain or with additives) continuously for at least 20 minutes. Under paragraphs 3.2.4 and 3.3.1, capacity should be based on the one section that needs the most water, rather than on several sections running at once. As a minimum, it should cover a section over the biggest single engine, generator set or other machine.
Where a machinery space contains multiple engines, paragraph 3.2.4 advises arranging at least two sections. Under paragraph 3.3.5, the local-application installation may be fed from a water-based main extinguishing system's supply, provided sufficient quantity and pressure run both installations across their full required duration.
Automatic-release guidance sits in paragraph 3.1.5. Where automatic release is fitted, a warning notice should sit outside each entry point naming the extinguishing medium and warning of the possibility of automatic release (3.1.5.1). Automatic triggering should use two approved flame detectors (3.1.5.2.1), one approved flame plus one approved smoke detector (3.1.5.2.2), or another Administration-accepted arrangement (3.1.5.2). Heat detectors are generally not advised here (3.1.5.2).
Under 3.1.5.3, a single active detector should raise an alarm only, unless the Administration accepts another arrangement. Two or more active detectors initiate release alongside audible and visual section-activation alerts at both the ECR and either the navigation bridge or a staffed central control station (3.1.5.4). Manual release controls should sit at accessible positions inside (unlikely to be isolated by a protected-area fire) and outside the space (3.1.3), with displayed operating instructions (3.1.6). Where fixed aerosol or high-expansion foam systems are fitted, paragraph 3.1.7 advises operational measures or interlocks to prevent local-application discharge from interfering with their effectiveness.
Installation guidance also covers pumps, electrics, and piping. Pressure-source components should sit outside protected areas (3.1.4). If pressure-source electrical components sit inside the protected space, they should have at least IPX4 protection, and main power suffices for external-power units (3.3.4). Discharging freshwater mist is not intended to impose requirements on electrical equipment inside the protected area (3.1.2). Pipe sizing should follow a hydraulic method such as Darcy-Weisbach or Hazen-Williams (C = 100 black or galvanised mild steel, C = 150 copper, copper alloys, or stainless steel, 3.2.3). Piping should also carry an air-blow fitting to check for obstructions (3.3.8).
3. Nozzle Geometry (Circ.1276/Rev.2) & Type-Approval Test Limits
On 22 January 2025 (following MSC 109), IMO published revised unified interpretations Circ.1276/Rev.2 (superseding Rev.1) as recommendatory guidance for ships contracted for construction on or after 4 December 2024. Revision 2 updated duct-separation rules under regulation 9.7.5.1 of SOLAS Chapter II-2 while retaining II-2/10.5.6 Sketches 1.1 through 1.5 on outer-nozzle placement. A footnote clarifies that MSC/Circ.913 gave way to Circ.1387 and Corr.1.
Outer-nozzle layout follows the tested grid under Circ.1387 Appendix 3.4.2 and Circ.1276/Rev.2 Sketches 1.1 to 1.5. Where a 3 x 3 grid passed fire positions 3.3.2.1 to 3.3.2.3 (3.4.2.1), or a single row passed the same positions (figure 3.4.2.5), outer nozzles should sit at least D/4 outside the protected area. D is the maximum tested nozzle spacing. For 2x2 or 3x3 grids under 3.4.2.2 (fire scenarios 3.3.2.3 through 3.3.2.5), outer nozzles can be located at or outside the perimeter. Under the unified interpretation, a single nozzle sits above the fire source at the centre of a D/2 by D/2 area (Sketch 1.5 and Appendix 3.4.2.4). Next to a bulkhead, Appendix 3.4.2.5 puts the first nozzle row D/2 away from it.
Engineers should separate Circ.1387 Appendix laboratory test-rig parameters from shipboard operating limits. Where a test room is used, it needs a floor area of 100 m² or more and a height of 5 m or more. Oxygen there should stay over 20% by volume for the first 5 minutes after ignition (3.2.1). Approval fires burn nominal 6 MW (8 bar, 0.16 kg/s ± 0.01) and 1 MW (8.5 bar, 0.03 kg/s ± 0.005) horizontal light diesel sprays at 20 ± 5 °C. Pre-burn runs 10 to 15 seconds after ignition before water activation (4.1). Extinguishment should happen inside 5 minutes of water application (4.3.2), with fuel spray continuing at least 15 seconds (4.3.3) and water discharge at least 1 minute (4.3.4) after extinguishment.
System components also undergo type-approval durability testing under Circ.1387. On a working ship, the shortest and longest allowed nozzle-to-hazard distances, any nozzle angles, the spacing D and the minimum operating pressure all come from the maker's approved manual and the type-approval test report. See Appendix 3.1.2, 3.3.1 and the test report contents. Ship-size limits come from SOLAS II-2/10.5.6.1, not from the circular.
Under SOLAS II-2/14.2.1.2, readiness is a statutory duty: the ship's fire-fighting equipment must stay in good working order and be available for immediate use. Regulation 14.2.2.1 bases maintenance, testing, and inspections on IMO guidelines, while 14.2.2.2 mandates keeping an onboard maintenance plan available for Administration inspection (with 14.2.2.3.3 covering fixed fire-extinguishing systems). The governing IMO maintenance guidelines are MSC.1/Circ.1432 (issued 31 May 2012), updated through Circ.1516 (issued 8 June 2015).
Both circulars use advisory wording, yet once embedded inside the ship's SOLAS II-2/14.2.2 maintenance plan and ISM planned maintenance system, a missed interval can be raised as a finding at an audit or survey. Log weekly, monthly, quarterly, annual, five-year, and ten-year checks with measured readings rather than bare signatures.
Weekly rounds (Circ.1432 paragraphs 4.7.1 to 4.7.3 plus 4.1) check control-panel indicators and alarms and visually inspect the pump unit and its fittings. Crew also verify non-locked pump-unit valves stand in normal service positions and test fire-detection panel indicator lamps.
Monthly checks (5.4.1 to 5.4.5 plus 5.10) verify control, pump, and section valve alignment (.1), inspect pressure tanks or other supply means (.2), and check automatic pump starting on pumps designed for auto-start (.3). Engineers also read standby pressure gauges and air or gas pressure gauges (.4), and test a rotating sample of section valves for alarm and flow so every valve is checked within 1 year (.5). Detection loops follow paragraph 5.10 so all detectors and manual call points are tested within 5 years, with the Administration setting sample sizes on very large systems.
Quarterly servicing centres on paragraph 6.5, introduced by MSC.1/Circ.1516 (original Circ.1432 had zero quarterly water-mist entries). Every three months, crews should assess header-tank and pump-unit water quality against manufacturer guidelines (6.5) and keep water-quality records on board as the maker's guidelines ask (3.4).
Annual servicing (7.5.1 to 7.5.18 plus 7.2.1) covers section test valves (.1), visual inspection of accessible components (.2), high-pressure cylinder condition and hydrotest dates (.3 to .4), alarms (.5), and pump flow and pressure (.6). Crews also verify antifreeze protection (.7), other water-supply cross-connections (.8), relief valves (.9), strainers (.10), valve positions (.11), emergency power switchover where applicable (.13), physical obstructions (.15), and automatic-release fire detection (7.2.1).
Watch two calendar traps inside Circ.1432 and Circ.1516. First, blowing dry air or nitrogen through dry-pipe headers (or otherwise proving them clear) is an annual task under paragraph 7.5.12, not a two-year job like fixed-gas piping (8.1.2). Section 8 contains zero two-year entries for water-mist or sprinkler systems. Second, for open-head local-application installations, Circ.1432 paragraph 7.5.16 advises flowing water through at least one section each year so every section is wet-tested within 5 years.
Every 5 years, Circ.1516 replacement paragraphs 9.3.2 to 9.3.4 advise internal inspection of all control and section valves (9.3.2) and testing section water quality unless already checked under 7.5.18 within 5 years. Crews also check system batteries or renew them per maker guidance (9.3.3), and check baseline water quality whenever each section is drained or flushed and refilled (9.3.4). Paragraph 9.3.1 applies to ro-ro deck deluge piping rather than engine-room local application. Every 10 years, paragraph 10.2 advises hydrostatic testing and internal examination of gas and water pressure cylinders to flag guidelines or, where none exist, EN 1968:2002 + A1. Unlike fixed gas in 10.1.1, paragraph 10.2 has no 10% sampling rule.
5. Water Quality, Pipe Fouling & Automatic Head Flowchart Escalation (Circ.1516)
Fine-droplet water-mist nozzles have narrow internal passages, which can foul if steel pipework sheds rust scale or the header tank water deteriorates. Clean strainers annually (Circ.1432 7.5.10) and test header-tank and pump-unit water quality quarterly against manufacturer guidelines (Circ.1516 6.5 & 3.4). Verifying dry open-head lines clear via the air-blow fitting (Circ.1387 3.3.8 & Circ.1432 7.5.12) keeps spray atomisation dependable.
Engine-room officers must separate open-head local-application nozzles from wet-pipe automatic (thermal-bulb) sprinkler and water-mist installations. Open-head local-application branches stay dry downstream of the section valve and follow annual open-section wet rotation (7.5.16) plus annual dry air or nitrogen blow-through (7.5.12). Automatic bulb-activated heads fitted in machinery or accommodation spaces follow Circ.1516 paragraphs 3.4, 7.5.14, 7.5.17, and 7.5.18.
Under Circ.1516 paragraph 7.5.17, ships test automatic water-mist or sprinkler heads at static or standby pressure using a two-branch failure flowchart. On installations younger than 5 years, crews sample 2 random heads per type (manufacturer model), and any single failure jumps straight into the 20-head Basic Testing tier. Once a system has been on board for 5 years or more, Basic Testing tests 2 random heads per section in 10 sections, 20 heads in total for each type.
Two separate escalation paths govern that 20-head sample. On the type-level branch, if 3 or more of 20 fail (R_FB of 15% or higher), sampling moves to Part 2 Extended testing under Case 1 (15% to 20%) or Case 2 (above 20%). Separately, on the section-level branch, if both tested heads fail in any section, crews test 10 additional heads in that affected section. If 2 or more of those 10 fail, all heads in that section are replaced. Paragraph 7.5.18 pairs head sampling with section water-quality checks, while 7.5.14 adds annual visual inspections in aggressive atmospheres or physical-damage zones so visibly damaged or painted heads are replaced outside the 7.5.17 count.
Begin every pre-survey round by comparing the approved nozzle layout plan against physical machinery-room alterations. Added exhaust lagging, overhead cable trays, lifting beams, or modified fuel-oil booster skids can shield boiler fronts, purifier bowls, or auxiliary-engine cylinder heads. Look for new obstructions at the annual check (Circ.1432 paragraph 7.5.15), clear them and verify outer-nozzle offsets match the approved Circ.1387 and UI Circ.1276/Rev.2 plan.
Where automatic release is installed, check outside every Category A entry point for legible medium and automatic-release notices (Circ.1387 3.1.5.1). Confirm displayed operating instructions (3.1.6) match the SOLAS II-2/15.2.4 Fire Control Plan. Inspect accessible manual release controls both inside and outside the space (3.1.3), confirming intact break-glass covers, valve tags, and schematic diagrams.
Before running the annual open-head water-flow test under Circ.1432 7.5.16, confirm freshwater versus seawater supply and protect nearby open electrical cabinets where prudent. Check bilge-well pumping readiness, and use the air-blow fitting (Circ.1387 3.3.8) during testing to confirm dry headers and nozzles stay clear of obstructions (7.5.12). Whenever any wet section is drained or flushed and refilled, record a fresh baseline water-quality check under Circ.1516 9.3.4.
Verify the automatic-release detection loop carefully with discharge safely isolated per maker procedure during routine trials (7.2.1). Prove that one active detector raises an alarm only (3.1.5.3), unless another Administration-accepted arrangement applies. Confirm two qualifying detectors trigger release, give visual and audible alarms in the space being protected and at the stations that are always manned (10.5.6.4 and 3.1.5.4). Where the space also has high-expansion foam or aerosol, check the interlock or operating measure that stops the local system spoiling it (3.1.7).
Finish the pre-survey audit by checking spare nozzle inventory, strainer baskets, pump cut-in logs, relief-valve entries, and standby gauge calibration dates. Verify 10-year hydrostatic test and internal examination certificates for every gas and water pressure cylinder (10.2). File signed sheets inside the SOLAS II-2/14.2.2 maintenance plan for Flag and PSC review.
Inside the 2025 IMO HSSC survey guidelines, Resolution A.1207(34) (3 December 2025), no standalone checklist row carries the label SOLAS II-2/10.5.6 or local application. Instead, Flag and Class surveyors verify engine-room water-mist installations under the machinery-space fixed fire-extinguishing, detection, and maintenance sections citing SOLAS II-2/10.4, II-2/10.5, FSS Chapters 5, 6, and 7, II-2/14, and II-2/7.
During Cargo Ship Safety Equipment surveys, audit Initial items (EI) 1.1.1.4 (excluding 10.5.5), 1.1.1.6, 1.1.4.5, 1.1.4.6, 1.1.4.9, and 1.1.7.1 to 1.1.7.3. Annual checks sit under (EA) 1.2.1.9 to 1.2.1.12, 1.2.2.5 to 1.2.2.6, and 1.2.2.9. Periodical item (EP) 1.3.2.2 checks that fixed-system pipework has been shown to be clear, while (EP) 1.3.2.4 tests fire detection, and Renewal item (ER) 1.4.2.1 carries (EP) 1.3.2 forward. Passenger Ship Safety surveys use parallel lines under Initial (PI) 5.1.1.13, 5.1.3.75, 5.1.3.76, and 5.1.5.10 to 5.1.5.12, plus Renewal lines (PR) 5.2.1.16 through 5.2.1.19, 5.2.2.71, 5.2.2.78, and 5.2.2.80.
Under the 2025 IMO PSC procedures, Resolution A.1206(34) (3 December 2025), Appendix 2 Section 5 (Areas under SOLAS 1974) lists conditions that may warrant detention of the ship. SOLAS Item 6 covers absent, non-compliant, or heavily deteriorated fire detection, fire alarms, or fixed fire-extinguishing installations unable to serve their intended use. SOLAS Item 2 addresses insufficient engine-room cleanliness and oil-contaminated piping insulation, while Item 13 covers serious deficiencies in operational requirements under Appendix 7.
Appendix 6 paragraphs 3.2 and 3.3 flag machinery maintenance faults such as oil leaks, disconnected trips, and faulty alarms, while 6.1 covers poor engine-room cleanliness and major fire-extinguishing defects and 6.4 addresses obstructed escape routes. Paragraph 11 requires extra safety gear beyond convention or flag rules to work when relied on, or else undergo repair, removal, or (where removal is impracticable) clear inoperative marking and securing. Under Appendix 7 Part 1, paragraph 4.6 checks communications between the safety centre, central control station, bridge, ECR, fire-extinguishing storage rooms and fire equipment lockers. Paragraph 5.1 notes detention may be considered if crew are unfamiliar with fixed fire-fighting release starting positions, operation, or engine-room fire alarm indicator locations. Part 2 checks consolidated instructions (1.4.2.1), fire-drill manning (2.5.4), and current Fire Control Plans (2.10). Keep endorsed statutory safety certificates (Appendix 12 Part A Items 3 and 5) and required onboard fire documents (Appendix 12 Part B Items 13, 14, 15, 17, and 49) current.
Frequently Asked Questions
Can an engine-room water-mist local-application system replace the main fixed CO2 or FSS Ch. 7 system?
No. Under SOLAS II-2/10.5.6.1 to 10.5.6.2 (ships built on or after 1 July 2002), passenger ships of 500 GT or above and cargo ships of 2,000 GT or above need this protection in Category A spaces above 500 m³. The approved local-application water-based (or equivalent) system supplements the main fixed plant under 10.5.1.1 without stopping engines, evacuating personnel, or closing off the space.
Which internal combustion engines must be protected before and after 1 July 2014?
IMO Resolution MSC.338(91), effective 1 July 2014, widened SOLAS II-2/10.5.6.3.1 so ships built on or after 1 July 2014 protect fire-hazard parts of internal combustion machinery in the space. Where 10.5.6 applies to earlier builds, 10.5.6.3.1 covers main-propulsion and power-generation internal combustion machinery, alongside boiler fronts, incinerator fire hazards, and purifiers for heated fuel oil.
Must the water-mist supply tank handle two machinery-space sections discharging simultaneously?
No. Under IMO guidance MSC.1/Circ.1387 paragraphs 3.2.4 and 3.3.1, the supply should last at least 20 minutes for the one section needing the most water. As a minimum, that section covers the biggest single engine, generator set or other machine. Multi-engine spaces divide into two or more separate sections (3.2.4). A local-application system fed from a water-based main extinguishing supply should have sufficient quantity and pressure to run both installations across their full required duration (3.3.5).
How often must dry-pipe local-application piping be blown through and open-head sections flowed?
Under IMO guidelines Circ.1432 and Circ.1516, crews blow dry air or nitrogen through dry-pipe headers annually (7.5.12), not every two years. Open-head water-mist installations flow water through at least one section yearly so every section is wet-tested within 5 years (7.5.16). Section 8 holds zero two-year water-mist tasks.
Did IMO Resolution MSC.403(96) add mandatory water-quality rules to SOLAS II-2/10.5.6 or FSS Code Ch. 7?
No. MSC.403(96), effective 1 January 2020, replaced FSS Code Chapter 8 paragraph 2.4.1 with 2.4.1.1 and 2.4.1.2 for automatic sprinklers protecting accommodation, control stations, and service spaces, plus added Chapter 17. Engine-room water-mist water-quality checks sit inside IMO guidelines Circ.1516 (paragraphs 3.4, 6.5, 7.5.18, 9.3.2, and 9.3.4) implemented through the SOLAS II-2/14.2.2 maintenance plan.
How does MSC.1/Circ.1516 automatic sprinkler and water-mist nozzle testing escalate on older ships?
Under Circ.1516 paragraph 7.5.17, automatic heads are tested at static or standby pressure. Under 5 years old, crews sample 2 random heads per type, and any failure jumps directly to 20-head Basic Testing. At 5 years and older, Basic Testing samples 2 random heads per section in 10 sections (20 heads in total for each type). If 3 or more of 20 fail (15% or higher), sampling escalates to Part 2 Extended testing under Case 1 (15% to 20%) or Case 2 (above 20%). Separately, if both heads fail in one section, test 10 more heads in that section and replace all heads there if 2 or more fail, alongside section water-quality checks (7.5.18).